Page 221 - Subyek Teknik Mesin - Forsthoffers Best Practice Handbook for Rotating Machinery by William E Forsthoffer
P. 221

Compressor Best Practices   Best Practice 3 .22
                                                                   Example 2: Contact type gas side seal e bushing
                                                                   type atmospheric seal with orificed through flow
                                                                   The only difference between this type of system and the pre-
                                                                   vious system is that the back pressure is maintained constant by
                                                                   a permanently installed through flow orifice. As a result, the
                                                                   differential pressure control valve is installed on the inlet side of
                                                                   the system. The process gas reference is still the same as before,
                                                                   that is, to the highest pressure side of the compressor.
                                                                   Figure 3.22.10 shows this type of system.
                                                                     Let us examine the previous example case for this system and
                                                                   observe the differences.

                                                                   1. Gas Side Seal Flow ¼ 0
                                                                   2. Atmospheric Side Seal Flow
                                                                     Reference Pressure ¼ 0
                                                                     Seal Flow ¼ 19.25 liters/min (5 GPM)
                                                                     Reference Pressure ¼ 1,380 kPa (200 PSIG)
                                                                     Seal Flow ¼ 46 liters/min (12 GPM)
                                                                   3. Flow Through Flow (Orifice)
                                                                     Minimum ¼ 2 liters/min (0.5 GPM)
                                                                     Maximum ¼ 11.5 liters/min (3 GPM)
                                                                     As can be seen, this system is more susceptible to high tem-
                                                                   perature atmospheric bushing conditions at low suction pres-
                                                                   sures, and must be observed during such operation to ensure
                                                                   integrity of the atmospheric bushing. In this system, the control
                                                                   valve will sense supply oil pressure to the seal chamber and
                                                                   control a constant set differential, approximately 241 kPad (35
                                                                   psid), between the reference gas pressure and the supply pres-
                                                                   sure. If continued low pressure operation is anticipated with
                                                                   such a system, consideration should be given to a means of
                                                                   changing the minimum flow and maximum flow orifice for var-
                                                                   ious operation points. Externally piped bypass orifices could be
              Fig 3.22.9   Compressor shaft seal (Courtesy of IMO Industries)
                                                                   arranged such that a bypass line with a large orifice for minimum
                                                                   suction pressure conditions could be installed and opened during
              1. Gas Side Seal Flow ¼ 0                            this operation. It is important to note, however, that the entire
              2. Atmospheric Side Seal Flow                        supply system must be designed for this flow condition and the
                Reference Pressure ¼ 0                             control valve must be properly sized to ensure proper flow at this
                                                                   condition. In addition, the low pressure bypass line must be
                Seal Flow ¼ 19.25 liters/min (5 GPM)
                Reference Pressure ¼ 1,380 kPa (200 PSIG)          completely closed during normal high pressure operation.
                Seal flow ¼ 46 liters/min (12 GPM)
              3. Flow Through Flow                                 Example 3: Bushing gas side seal e bushing
                Minimum ¼ 11.5 liters/min (3 GPM) e occurring at high  atmospheric side seal with no flow through
                ATM bushing flow ¼ 46 liters/min (12 GPM)           provision
                Maximum ¼ 46 liters/min (12 GPM) e occurring at low
                ATM bushing flow ¼ 11.5 liters/min (3 GPM)          Figure 3.22.11 shows this type of seal system. Here, the differ-
              4. Seal Oil Supply Flow in both cases ¼ 57.8 liters/min (15  ential control valve becomes a level control valve sensing differ-
                                                                   ential from the level in an overhead tank and is positioned
                 GPM)
                                                                   upstream of the unit. Both bushings can be easily conceived as
                As shown in the previous example, the required seal oil  equivalent orifices. The gas side bushing flow will remain constant
              supply at maximum operating speed required to remove fric-  regardless of differential. The atmospheric bushing flow will vary
              tional heat is 57.8 liters/min (15 gal/min). At start-up, low  according to seal chamber to atmospheric pressure differential.
              suction pressure conditions, the control valve must open to  The atmospheric bushing must therefore be designed to pass
              allow an additional ten gallons per minute flow through to the  a minimum flow at minimum pressure conditions that will
              seal chamber. At maximum operating pressure, however, the  remove frictional heat and thus prevent overheating and damage
              valve only passes a flow of three gallons per minute since 46  to the seal. Since a gas side bushing seal is utilized, a minimum
              liters/min (12 gal/min) exit through the atmospheric bushing.  differential across this orifice must be continuously maintained.
              This type of system is less sensitive to low suction pressure  Utilizing the concept of head, the control of differential
              operation, since flow through oil will remove frictional heat  pressure across the inner seal is maintained by a column of
              around the atmospheric bushing.                      liquid.

                                                                                                               195
   216   217   218   219   220   221   222   223   224   225   226