Page 223 - Subyek Teknik Mesin - Forsthoffers Best Practice Handbook for Rotating Machinery by William E Forsthoffer
P. 223

Compressor Best Practices   Best Practice 3 .22
















































              Fig 3.22.11   Typical seal oil system (Courtesy of M.E. Crane, Consultant)

              atmospheric bushing at this higher differential pressure condi-  a head tank level transmitter, and is installed downstream of the
              tion. Utilizing the concept of equivalent orifices, it can be seen  seal chamber. This system functions in exactly the same way as
              that the additional differential pressure across the atmospheric  the system in Example 1, the only difference being that a level
              bushing orifice is compensated for by reducing the effective  control valve in this example replaces the differential control
              orifice area of the bypass control valve. This is accomplished by  valve in that example. Both valves have the same function; that
              sensing the level in the head tank and maintaining it at a constant  is, to control the differential in the seal chamber between the
              value by opening the seal oil supply valve.          seal oil supply and the referenced gas pressure. A level control
                As in the case of the orificed through flow example above, this  valve is utilized here, however, since a bushing seal requires a
              configuration is susceptible to high atmospheric bushing temper-  significantly lower differential between the seal oil supply
              atures at low suction pressures and must be monitored during this  pressure and the gas reference pressure.
              condition. Repeated high temperatures during low suction pres-  Consider the following example. Assume that a differential
              sure conditions should give consideration to re-sizing of atmo-  control valve would be used as opposed to a level control valve
              spheric bushing clearances during the next available turnaround.  for the system in Figure 3.22.11. For the start-up case, the
              The original equipment manufacturer should be consulted to  differential control valve would have to maintain a differential of
              ensure correct bushing sizing and supply system capability.  34.5 kPa (5 psi) over the reference gas. When the reference gas
                                                                   pressure was 0, the oil upstream pressure to the valve would be
                                                                   approximately 34.5 kPa (5 psi). For the operating case, main-
              Example 4: Gas side bushing seal e atmospheric       taining the same 34.5 kPa (5 psi) differential, the upstream
              side bushing seal with through flow design
                                                                   pressure across the valve would be approximately 1,413 kPa
              Refer to Figure 3.22.11. The only difference between this and  (205 psi) instead of 34.5 kPa (5 psi). Consequently, the valve
              the previous system is that a through flow option is added, to  position would change significantly, but still would have to
              allow sufficient flow through the system during changing pres-  control the differential accurately to maintain 34.5 kPa (5 psi).
              sure conditions. The bypass valve in the previous system is  Reduction of this pressure by any amount below 34.5 kPa (5 psi)
              replaced in this system by a level control valve referenced from  could result in instantaneous bushing failure. However, if a level

                                                                                                               197
   218   219   220   221   222   223   224   225   226   227   228