Power Supply Systems  Chapter | 11    343


             11.4  SWITCHING EQUIPMENT
             11.4.1  Switching Equipment for Experimental Facilities

             Switching equipment allows for generation of the initial voltage at breakdown
             and plasma current initiation and for energy discharge from the superconduct-
             ing magnets at the quench. In both cases, it is necessary to quickly open a
             high-inductance circuit, which transmits direct current of a few tens of kiloam-
             peres. This task usually involves upgrading of existing commercial switches or
             development of unique purpose-made switching devices [10].
                When the main circuit opens, the current from the coil is switched to the
             resistor connected in parallel to a CB. The CB is either a high-current mechani-
             cal switch, a vacuum switch or a static device based on semiconductor devices,
             such as a thyristor with artificial suppression system or an integrated gate-
             commutated thyristor (IGCT; Table 11.8). The CB type is chosen on the basis of
             specific operational requirements.
                In the PS system of the JET inductor the current is switched into the energy
             discharge resistor by two mechanical switches with forced air flow at 80 atm
             [7]. At an initial current of 80 kA a voltage of 40 kV appears on the coil. The
             main disadvantage of this version is the limited lifetime of the switches and
             the necessity to maintain them frequently, as the contacts suffer erosion under
             the action of electrical arc.
                In the Ricerca Formazione Innovazione (RFX) machine, high-current keys
             based on VCBs are employed to switch current into the resistors [11]. Compared



               TABLE 11.8 Main Characteristics of Switches for Energy Discharge Circuit

               Facility        JET                RFX           KSTAR
                                             Circuit breaker type
                               Mechanical AIR-    Vacuum circuit   IGCT circuit
               Parameters      blast circuit breaker  breakers  breaker
               Nominal         80                 70            25 (PF1–PF4)
               current (kA)                                     20 (PF5, PF6)
               Nominal voltage   40               17.5          3 (PF1–PF4) 6
               (kV)                                             (PF5, PF6)
               Breaking time (ms)  2              30            100 (operation
                                                                time)
                                 10
                                        10
               Max current action   10  (3 × 10  in   2.3 × 10 9  —
                      2
               integral (A s)  abnormal mode)
               Energy absorbed by   200/120       150           —
               resistors (MJ)
               RFX, Ricerca formazione innovazione.