Page 122 - Industrial Power Engineering and Applications Handbook
P. 122

Static controls and braking of  motors  611 03

















           1   10   20   30   40   50   60   70   80  90 Hz
               Below the base speed  -Above   the base speed
                                                            0      0 25f1    O.5Of1   0 75f1   1 OOf,
                       Frequency (Speed)  4
                                                                    Ns4      Ns3      Ns2      Ns 1
                                                                           Speed
              *  Drooping torque at lower speeds. At higher   0 Tst1  =   1   0 Tst2 =   1
                speeds too, the torque profile is variable
                                                                   1                 1
                                                           0 Ts13=  0.5f    0 Ts,4=  0.25f
                                                                              (V/f control &,,  constant)
         Figure 6.2  Actual speed-torque  characteristics  by a conventional
         frequency control (V/f control)                      Figure 6.3  Speed variation at constant torque




















                                                      Speed -
                                s= 1



                                                 (Variation in frequency)
                                       Figure 6.4  Speed variation at constant  HP

         Application                                   during a load variation (see Example 6.1 for more clarity).
                                                       Rating, however, is no bar.
         In a V/fcontrol  generally, only the frequency is vaned to
         obtain the required speed control. Based on this frequency,
         the switching logistics of the inverter control circuit control   6.4  Phasor (vector) control
         the inverter’s output voltage using the PWM technique
         to maintain the same ratio of V/f. A Vlfcontrol is, however,   A simple V/fcontrol,  as discussed above, will  have  the
         not suitable at lower speeds. Their application is limited   following limitations:
         to fan, pump and compressor-type loads only, where speed
         rcgulation  need  not  be  accurate,  and  their  low-speed   Control at very low speeds is not possible.
         performance or transient response is not critical and they   0  Speed control may not be very accurate.
         are also not required to operate at very low speeds. They   0  Response  time  may  not  be  commensurate  with  the
         are primarily used for soft starts and to conserve energy   system’s fast-changing needs.
   117   118   119   120   121   122   123   124   125   126   127