Page 249 - Industrial Power Engineering and Applications Handbook
P. 249

9/228  Industrial Power Engineering and Applications Handbook
       void  and  the  remaining  voltage  across  the  insulation
       (dielectric). When the applied voltage is increased, the
       air of  the void at a certain  value of the applied voltage
       will break down, causing an internal discharge. The void
       is now  short-circuited  and the full  voltage  will appear
       across  the  insulation  (dielectric).  The  tan  6 - voltage
       curve  at  this  point,  where  ionization  begins,  shows  a
       rapid change (Figure 9.8). In practice, an insulation system,
       whether of a coil, winding or a slot, will always contain
       many  small voids, often  located  at different  depths of
       the dielectric. The higher the number of voids, the steeper
       will be the tan 6V curve beyond a certain voltage level
       (Figure 9.8). The value of  tan 6 at low voltage and the
       rate of change of tan 6, i.e A tan 6, with an increase in
       the applied test voltage, gives an indication of the condition
       of the dielectric at higher test voltages, and also suggests
       the presence of moisture. Hence, A tan 6 is a measure of
       voids in the insulation  system and indicates the quality
       of  curing.  It  is  also  a good  method  of  monitoring  the   Figure 9.9  A NEMA spray test being carried out on a stator
       quality of insulation of HT formed coils during the course   winding (Courtesy: BHEL)
       of manufacture. This is also useful in analysing the ageing
       condition  of  an insulation.  The methods  and norms  of
       acceptance  limits  are  dealt  with  in  IEC  60894.  For   9.6.2  Wet test of resin-poor windings
       acceptance norms see Table 1 1.5.
                                                      MG- 1-20.48 recommends this test for large HT motors
                                                      that  are  resin-poor.  In  this  test  the  whole  stator  is
                                                      submerged  in  water,  if  possible,  and  a  10-minute
                                                      absorption test is carried out. If this is not possible, then
                                                      the windings are sprayed with water thoroughly, from all
                                                      sides for 30 minutes  (Figure 9.9). The water  is mixed
                                                      with a wetting agent to reduce its surface tension. During
                                                      the last 10 minutes of the test the insulation resistance is
                                                      measured at 500 V d.c, which should not be less than as
                                                      indicated in equation (9.1). If it is acceptable, the windings
                                                      are  then  subjected  to  an  a.c.  high-voltage  test  at  1.15
                                                      times the rated voltage for 1 minute while the windings
                      Voltage (V,) -                  minute insulation  resistance reading using a 500 V d.c.
                                                      are still being sprayed. After the high-voltage test, the 1
                                                      source is obtained. This should not be less than as specified
                                                      data for the site tests.
          Figure 9.8  Variation in tan 6 with the applied voltage   in equation (9.1). This value will then form the reference

                                             Relevant Standards

       IEC              Title                                     IS               BS
       60034- l/1996    Rotating electrical machines              472211992.  32511996   BS EN 60034-1/1995
                        Rating and performance for rotating machines
       60071-1/1993     Insulation coordination. Definitions, principles and rules   2165 (Part-I) 1991 and  BS EN 60071-1/1996
                                                                  2165 (Part-11) 1991
       60085/ 1984      Thermal evaluation and classification of  electrical insulation   I27 1/1990   BS 2757/1994
       60894/1987       Specification for the insulation of bars and coils of high   -   BS 4999-144/1987
                        voltage machines,  including  test methods
                                   Relevant US Standards ANSI/NEMA and IEEE
       ANSUIEEE13 13.1/1996  Insulation Coordination. Definitions, Principles and Rules
       ANSI/IEEE-I/1992   General  principles  for temperature limits in the rating of electric equipment and for the evaluation of  electrical
                        installation
       ANSIlIEE  101/1987   Guide for the statistical analysis of Thermal Life Test data
       NEMA/MG.1/1993   Motor and generators ratings, construction, testing and performance
   244   245   246   247   248   249   250   251   252   253   254