Page 449 - Industrial Power Engineering and Applications Handbook
P. 449

Testing of metal-enclosed switchgear assemblies 14/423
       Table 14.2  For series II voltage systems
       Insulation levels, power frequency and impulse withstand voltages for metal-enclosed switchgear assemblies

       Nominal  system   Rated maximum   One-minute power frequency   Standard  lightning  impulse   One-minute d.c. voltage
       voltage      ,  system voltage   voltage withstand at a   (1.2/50 p) voltage withstand   withstand (phase to
                                    frequency not less than the   (phase to ground)   ground)
                                    rated 60 Hz (phase to ground)
       I              2             3                      4                      5

       kV (r.m.s.)    kV (r.m.s)
       ~
                                    b          c           b          C           b           c
        0.48           0.508         2.2        -            -          -          3.1         -
        0.6            0.635         2.2        -            -          -          3.1         -
        4.16           4.16         19.0       19           60         60         21          21
        1.2a           8.25         36.0       26.0         95         75         50          31
        13.8          15.0          36.0       36.0         95         95                     50
        14.4        1  15.5          -         50.0          -        110                     IO
       23.0         1  ::::          -         60.0          -        125
       34.5                         80.0       80.0        150        150
       69.0           72.5           -        160.0          -        350
       aANSI C-37/20C specifies this rating only for metal-clad switchgear assemblies and not for metal-enclosed bus systems.
       bWith breaker assemblies
       ‘With  isolator assemblies
       Based on ANSI C-37/20C
       Notes
       1  (a)  The procedure for a d.c. test is same as for a.c. Due to variable voltage distributions when conducting d.c. tests, the ANSI Standard
             recommends that the matter may be referred to the manufacturer for system voltages 25.8 kV and above.
          (b)  For a power frequency voltage withstand test, the d.c. test is generally not recommended on a.c. equipment, unless only d.c. test
             voltage is available at the place of  testing. The d.c.  test values, as provided  above, are therefore for such cases only  and are
             equivalent to power frequency a.c. voltage withstand test values.
       2   Power frequency tests after erection at site, if required, may be conducted at 75% of the values indicated above. Also refer to field tests
          (Section 14.5, Table  14.8).



       Table 14.3  For series I voltage systems. Dielectric test voltages   (i) For fixed as well as draw-out assemblies
       for control and auxiliary circuits and also LT power circuits   The trolley is in the service position in draw-out assemblies
                       ~          ~    ~              (Section  13.3.2).
       Nominal  auxiliary/power   One-minute power frequency
       voltage                 voltage withstand at any
                              frequency between 45 and   1  Between  phase to phase  and each phase  to ground
                               65 Hz (between phases and   with the switching devices in the closed position
                               ground)                2  Between  phase  to phase  and  each phase  to  ground
                                                         with the switching devices in the open position. This
       Control and auxiliary circuits                    test is to be conducted on both line and load sides of
       1  Where the rated insulation   1000 V (r.m.s.)   the switching device.
         voltage does not exceed 60 V                 3  Between  the  line  and  the  load  terminals  of  each
       2  Where the insulation voltage   (2 V, + 1000) volts with a   phase, the main switching devices being in the open
         exceeds 60 V          minimum of  1500 V (r.m.s.).
                                                         position.
       Power circuits
       3  For voltages between 300   2500 V (rms)     (ii) For draw-out assemblies
         and 660 V
                                                      The trolley  is  in test position  and the  main  switching
       As in IEC 60439-1                              device in the closed position,
                                                      1  Between phase to phase and each phase to ground on
         raised  gradually but rapidly  and then  maintained at   both line and load fixed terminals.
         that level for one minute, reduced rapidly up to 50%   2  Between line and load fixed terminals of each phase.
         of its value and then disconnected.             ANSI-C37/20C recommends this test to be conducted
       5  During the test,  one pole of  the testing transformer   at a value 10% higher than specified in Table 14.2 for
         should be connected to ground and the frame of the   both power frequency and impulse voltage withstand
         assembly.                                       tests.
   444   445   446   447   448   449   450   451   452   453   454