Page 450 - Industrial Power Engineering and Applications Handbook
P. 450

14/424  Industrial Power Engineering and Applications Handbook

        (iii) Additional test requirements for outdoor HT   Measurement of temperature of enclosure,
        assemblies                                    insulation and current-carrying parts
        The following are a few additional test requirements for   The thermocouples or RTDs should be located such as
        an outdoor HT assembly, recommended by  IEC 60694   to measure the hottest spot, even if this means drilling a
        for rated voltages up to 100 kV.
                                                      hole in the current-carrying parts.
          Wet  test While an indoor type  switchgear asscmbly
          requires  only  a  dry  power  frequency  voltage  with-   Procedure
          stand test, the outdoor type switchgear assembly also   I  The test may be conducted on a completed assembly
          needs  a  wet  test  under  wet  conditions  to  check  the   of  a  switchgear or  a  controlgear or  a  part  of  it,
          external insulation. For the test procedure refer to IEC   whichever  may  be regarded  as  a  complete section.
          60060- 1.                                      The purpose  is  to achieve a  near-service condition.
          Artificial pollution test  The purpose of this test is to   To do this in a multi-section switchgear or controlgear
          provide information on the behaviour of the external   assembly it is advisable to test at least three vertical
          insulation while operating in pollutcd conditions. The   sections joined together and measuring the temperature
          test  may  be  performed  only  if  thought  necessary,   rise on the middle section. This is to restrict the extra
          depending  upon the degree  of  contamination  at  the   heat dissipation, through the sides, except natural heat
          place  of  installation.  For the  test  procedure  refer  to   transfer,  and  also  to  simulate  the  influence  of  heat
          IEC 60060- I.                                  transfer to this section through other sections.
          Test results   Any disruptive discharge or electrical   2  The test must be conducted at the rated* current, at a
          breakdown during the application of high voltage should   frequency  with a  tolerance of  +2% and -5%  of  the
          be considered  as a dielectric failure.        rated  frequency  and  the  voltage  in  a  sinusoidal
                                                         waveform, as much as practicable.  See also Section
        14.3.4 Impulse voltage withstand test (for system   11.3.2. The test is  carried out until  the temperature
              voltages 2.4 kV and above)                 reaches almost a stable state, i.e. when the variation
                                                         does not  exceed  1°C per  hour. To  shorten  the  test
        The impulse voltage is applied as shown in Tables 14.1   duration, the current may be enhanced during the initial
        and  14.2 for series I1 or Table  13.2 for series I voltage   period to reach a fast, stable state.
        systems,  with  a  full  wave  standard  lightning  impulse   3  Since  it  may  not  be  practical  to  create  the  actual
         1.2/50 p (Section  17.6.1) a  front time equal to or less   operating conditions  at the place  of  testing, normal
        than  1.2 ,LE,  and the crest value equal to or more than the   practice is to simulate these conditions on the following
        rated full wave impulse withstand voltage. According to   basis.
        ANSI  C-37/20C,  three  positive  and  three  negative   The heat generated by a current-carrying component
        impulses  must be  applied  without  causing  damage  or   or conductor is its watt loss and is expressed by I’R,
        flashover. Should a flashover occur in only one or any   where  I  is  the  current  and  R  the  resistance  of  the
        group  of  three  consecutive tests,  three  more  tests  are   circuit  under  consideration.  The  watt  loss  of  each
        allowed  to  be  conducted. If  the  equipment  passes  the   current-carrying  component  installed  in  the  test
        second  group  of  three  consecutive  tests,  it  should  be   assembly  is  estimated  and  added  to  arrive  at the
        considered as acceptable. The flashover which occurred   approximate  watt  loss  during  the  actual  operation.
        earlier may be considered as random and irrelevant.   Based  on this loss is calculated of  the total  heaters
                                                         required. These heaters  are then  suitably located in
         14.3.5 Verification of temperature rise limits (or   the  test  assembly  to represent  all the incoming and
              rated continuous current capacity)         outgoing feeders, their  power  cables and any  other
                                                         current-carrying component.
        The test  must  be  carried  out  indoors,  reasonably  free
         from draughts. Thermocouples should be used to measure   Sources generating  heat
         the  temperature,  and  the  ambient  temperature  can  be   1  Power circuits
         measured by thermocouples or thermometers.        Interrupting devices - switches, breakers, MCCBs,

        Measurement of ambient temperafure
         The  ambient  temperature  should  be  measured  during
        the last quarter of the test by at least three thermometers
         or thermocouples placed equally around the switchgear
         assembly, at almost the centre level and at about 1  metre
         from the body of the enclosure. The ambient temperature
         to be considered  must be the average of these readings
         and  should  be  within  10-40°C.  To  ensure  that  the
         ambient  temperature  is  unaffected  by  magnetic  field,
         alcohol  thermometers  must  be  used  and  not  mercury
         thermometers.
   445   446   447   448   449   450   451   452   453   454   455