Page 520 - Industrial Power Engineering and Applications Handbook
P. 520

15/494  Industrial Power Engineering and Applications  Handbook
           (iii) Temperature rise test
           (iv) Verification of dielectric properties on the primary
               windings to check the insulation level as in Tables   1  1
               13.2 and  14.3 for series I  and Tables  14.1 and   Sl   s2
               14.2 for series I1 voltage systems.     (1) Single ratio CT   (2) CT with an intermediate
            (a) Power  frequency  voltage  withstand  or  HV                tapping on the secondary winding
               test.                                       C.    C9
            (b) Impulse voltage withstand or lightning impulse
               test for system voltages 2.4 kV and above.
               Since a CT  is associated with a switchgear, either
               with its assembly or the switchyard, the above
               four  tests  are  almost  the  same as  those  for a
               switchgear assembly and as discussed in Chapter   s1   s2     1s1   Is,  2%   2s2
               14. The test requirements and procedure are also   (3) CT with a primary winding  (4)  CT with two secondaty windings,
               similar.                                   in  2 sections which may be   each with its own magnetic core.
            (v) Wet test for outdoor type transformer: This test   connected  in  series  or
                                                          parallel
               is similar to that  for a VT and as discussed  in
               Section 15.10.1(1).                         Figure 15.36  A CT wound in different combinations
            (vi) Verification of accuracy: the test results obtained
               must comply with the values of Tables 15.8 and
               15.9  for  a  measuring  and  a  protection  CT
               respectively.                                 achieve an appreciable deflection of the voltmeter
         2  Routine Tests  These will cover the following tests:   needle.
            (i)  (a)  Verification of terminal marking    (ii)  Power frequency withstand test on secondary
                  Refer  to  Figure  15.36, illustrating  types of   windings
                  transformer connections.                    The  secondary  windings  should be  capable  of
               (b) To check the polarity of a CT It is imperative   withstanding  a  rated  power  frequency,  short-
                  that  the  terminals  of  a  CT are  wired  with   duration withstand voltage of 3 kV for 1 minute.
                  correct polarity, with reference to the primary   (iii) Power  frequency  withstand  test  between
                  in each phase. A reversal in any phase will   sections
                  lead to incorrect meter readings, in metering   This  test  is  applicable  when  the  CT's  primary
                  CTs and erratic signals to the protective relays   and  secondary  windings  have  two  or  more
                  in protection CTs. Although CTs are marked   sections.  Then  the  section  in  between  will  be
                  with polarities by their manufacturers,  such   capable of withstanding a similar voltage as noted
                  as PI P2 for primary and SI S2 for secondary   in item (ii) above.
                  (Figure 15.36) it is possible, that by  human   (iv) Inter-turn overvoltage test
                  error at the time of fitting the CTs, care is not   This test is performed to check the suitability of
                  taken to maintain the same polarity in all the   the  inter-turn  insulation  to  withstand  the  high
                  three phases, or their connections are made
                  inadvertently,  without  ascertaining  their     Voltmeter
                  correct polarity. It is also possible that on a     or
                  reconnection,  such  as  at  site,  while        Ammeter
                  reassembling the modules of a switchgear or
                  a controlgear assembly, such an omission is
                  made. It is therefore advisable that the polarity
                  of  the  CTs  be  ascertained  at  site  before
                  commissioning  the  equipment,  such  as  a
                  switchgear  or a  controlgear assembly  or  a
                  switchyard utilizing a few CTs.         Primary         Secondary
               D.C.  voltage  test  to  ascertain  the polarity: A         terminals
               simple procedure to ascertain this is indicated in              l~l~l~+
               Figure  15.37. A  low  reading  d.c.  voltmeter  is   Pl   pz   D.C. source
               connected across the CT secondary windings and                 (6V-12V)
               a battery of 6-12  V through a switch across the
               primary. On closing the switch, the meter needle
               will  give a momentary flicker. If the polarity is
               correct, the flicker will be positive on connection
               and  negative  on  disconnection.  For  HT  CTs,
               mounted  on  transformer  bushings,  it  is   -0         Switch
               recommended  to  short-circuit  the  main
               transformer  secondary (LV) windings to reduce   Figure 15.37  Circuit to check the polarity of a bar primary CT
               the  overall  impedance  of  the  transformer  to   at site
   515   516   517   518   519   520   521   522   523   524   525