Page 516 - Industrial Power Engineering and Applications Handbook
P. 516

15/490 Industrial Power Engineering and Applications Handbook

        of 0.5 and above and a corresponding VA burden of 5 for
        a short-time current of 1 second. If these parameters are
        not suitable use the measuring CT with  a higher-rated
        primary current to meet the requirement.
          Similarly, for a protection CT from Table 15.11 choose
        an accuracy class of  10P5 with a VA burden  of 5  for a
        second short-time current. If this does not meet the need,
        the protection  CT may also have to be selected with a
        higher-rated primary current.


        15.8  Summary of specifications
              of a CT
        In Table 15.12 we listed the data, that a user must provide
        to  a  manufacturer  to  design  a  CT for  a  particular
        application.  Some of  the  data  chosen  are  arbitrary  to   Figure  15.34  Shorting  of  all  unused  CT  terminals  in  a  CT
        define the specifications.                     secondary circuit using a selector switch
                                                         For ease of analysis we have ignored (without much error)
                                                       the CT's own resistance and reactance.
        15.9  Precautions to be observed                 Total resistance of the instruments under rated condition
              when connecting a CT                                    =  7.5/5'

                                                                       =  0.3 R
           It is mandatory to ground the secondary circuit of the         11
           CTs (in a balanced 3$ system, the current through the    q= -x-    400
           neutral will be zero; see Section 21.2.2, Figure 21.7).       &    5
           It is required to eliminate the error due to accumulation   =  508.1  kV
           of  electrostatic  charge  on the  instruments  that  may   (a)  Under energized condition when the CT's secondary
           influence the readings. All  the CTs in a circuit must   is a closed circuit, voltage developed across the relay,
           be grounded at one point only otherwise circulating
           currents may raise the potential of the circuit, which   e;  =  circuit impedance  x 0.3
                                                                            e*
                                                                       ,
           is dangerous and may damage instruments or give the
           operator a shock or even trip other relays connected            508.1 x lo3   x 0.3
           in the circuit.                                           - (103.23 x lo3 + 1 + 0.3)
           One should not allow the CT secondary to be open          = 1.48 V
           circuited  when  it  is  energized,  for  it  may  induce
           dangerously  high  voltages.  This  phenomenon  is   (b)  Under energized condition when the CT's secondary
           explained in Example  15.8.                       is accidentally open circuited, the current will have
                                                             only the magnetizing path and the voltage induced
                                                             across the CT open terminals will be the same as
        Example 15.8                                         across the magnetizing circuit.  Under this situation
        To determine the terminal voltage of a CT during an accidental   the magnetizing circuit shall carry the same current
        open circuit under an energized condition consider a metering   as caused by the primary current, which is very high.
        CT connected across a few instruments. Refer to the following   :.  Voltage developed across the CT open terminals,
        figure  based  on  Figure  15.17, showing  an  equivalent  CT
        circuit referred to its secondary side.                 =   508.1 x lo3   x Ze
           We have assumed the following parameters,              (103.23  x lo3 + Ze)
           Connected Load  = 7.5 MVA                              [where  Z,  = Impedance of excitation circuit,]
           System Voltage  = 11 kV
                                                                                      1
                                                                                 1
           Burden of all instruments connected across the                    1  - 170 +J60
           CT = 7.5 VA                                                      Z,
           Lead resistance  = 2 x 0.5 R = 10           For simplicity, considering the approximate impedance of the
                            7.5 x  106                 excitation circuit (without much error) as J60 R
           Rated current,  I,  =
                          fix x 103                    ..         =    508.1 x  lo3   x J60
                              11
                        = 393.7 A                                   (103.23  x lo3 + J60)
           Consider a CT ratio of  = 40015 A                      = J295 V
                             11  io3                   which is approximately 200 times that of voltage under normal
           Load impedance  Z,  =                       condition and hence highly detrimental for the insulation of
                             45  x 393.7               the CT, the connecting leads and the human contact etc.
                           = 16.13 51                     Depending upon the system loading at the instant of  CT
           Z, referred to the secondary side  = 16.1 3 (400/5)2   circuit  interruption, it is possible that the primary current is
                                    = 103.23 kR        enough to cause a saturation of the CT core. When so, it is
   511   512   513   514   515   516   517   518   519   520   521