Page 511 - Industrial Power Engineering and Applications Handbook
P. 511

Instrument and control transformers: application and selection  15/485
                                                        high voltages across the CTs and the relay, particularly
                                                        during internal faults, when the CTs have the same polarity
                                                        and the spill currents are additive. As in IEC 60255-6, it
                                                        must be limited within 3 kV across the relay  circuit to
                                                        protect the CTs and the relay. An approximate formula
                                                        to  determine  the  likely  peak  voltage  across  the  relay
                                                        circuit is given by


                                                        where  Vp = peak voltage across the relay  and
                                                              V,,, = theoretical rnaxi~nurn CT secondary voltage
                                                                  across  the  relay  circuit  at  the  maximum
                                                                  internal fault current. (The maximum inter-
                                                                  nal fault current is the level of fault of the
                                                                  machine  or the  system  under  protection.)
                                                                  This must also take into account any other
                                                                  supply sources that may also feed the fault.
                                                                  such as more than one supply bus, as shown
                                                                  in Section  13.4.1(5) and Figure  13.18, and
                                                                  illustrated in Figure  15.30. If the cumulative
                                                                  fault current is I,,,,   then the maximum CT
                                                                  secondary voltage will be
           F, F3  - Through faults which may be much higher than at   V,, = lscc x impedance of the relay circuit.
                   F2 but outside the CTs  zone
             F2  - Internal fault being fed by two sources although   This can be limited by using a non-linear resistance called
                   limited by the equipment impedance   Metrosil"  across the relay, as shown in Figure 15.27. If
                                                        voltage reaches  a  dangerous  level, this  resistance  will
         Figure 15.30  An internal fault being fed by more than one source   provide a low-resistance parallel path to the current and
                                                        limit  the  voltage  across  the  relay  to  about  1  kV.  The
           The most severe fault is the capacity of the machine or   current I through the non-linear resistance is given by
         the  system  being  protected  to  feed  the  fault,  and  is   V,, = K  x Ip (K and p are constants)
         determined by its fault level  as indicated in Tables 13.7
         and  13.10. To  consider  a  higher  fault  level  than  this,   All these values are provided by the relay supplier when
         such as of the main power supply, is of little relevance as   this resistance becomes necessary.
         it would fall outside the detection zone of the CTs and
         would serve no useful purpose except to further improve   5 I Selecting  class PS CTs
         the stability level  of the protective scheme.
           Applying this scheme to system protection, where the   Ground fault protection of a machine and setting of the
         number  of  circuits  and  hence  the  number  of  CTs  are   relay. The following example illustrates the procedure to
         high.  will  mean  a high  POC (equation  (15.1)). A high   select class PS CTs for a typical G/F scheme. In practice,
         POC  may  not  be desirable,  as  it  may  underprotect  the   this  scheme would  be  more  appropriate for phase  and
         system. In such cases, it is advisable to divide the system   ground fault protections, as illustrated in  Figure  15.22.
         into  more  than  one  circuit  and  apply  the  scheme
         individually to all  such circuits (Example 15.6).
                                                        Example 15.5
                                                        Consider  a  generator,  10  MVA,  3.3  kV,  for  ground  fault
         3 Suppressing system harmonics                 protection having a sub-transient reactance  x;  = 12 f 10%
                                                        (Figure 15.29).
         Such relays are normally instantaneous, highly sensitive
         and operate at low spill  currents. Since they detect the   Grounding  method:   solidly grounded
         residual  current of the system, the current may contain   Overload capacity:   150% for 30 seconds (as in IEC
         third-harmonic  components (Section 23.6) and operate              60034-1 )
         the highly sensitive relay in a healthy condition. To avoid   Relay type:   differential
                                                        Rating:
         operation of the relay under such conditions, it is a normal   VA:   1A
                                                                            1, at the setting current,  lSt
         practice to supply the relay coil with a tuned filter, i.e. a
         series  L-C  circuit  to  filter  out  the  third-harmonic
         components. The  capacitance  of  the  filter circuit  may
         also tame a steep rising TRV (Section 17.10.3) during a   *This is a brand name given by the manufacturer of the non-linear
         momentary  transient condition and protect the relay.   resistor. a GEC group company in the UK. General Electric. USA
                                                        call it Thyrite, and similar names have been given to it hy different
                                                        manufacturers. Basically, it is a Sic non-linear resistance to provide
         4 Limiting the peak voltage                    the desired overvoltage protection. Refer to Section  18.1. I  for more
         As this is a high-impedance scheme, it can result in very   details.
   506   507   508   509   510   511   512   513   514   515   516