Page 510 - Industrial Power Engineering and Applications Handbook
P. 510

15/484  Industrial Power Engineering and Applications  Handbook
        these  quantities may be considered in phase with each
        other, with little error,
        :.  Isf = I,  -k  Ist
         If there are N number of CTs connected in parallel, the
        magnetizing current will flow through all of them. In a
        GF protection scheme all the three CTs of all the feeders
        being  protected  together  will  fall in  parallel,  while  in
        case of a combined GF and phase fault protection scheme,                          Non-linear
        only one third  of these CTs will fall in parallel. The CT                        resistor
        in the faulty circuit must be able to draw enough current                         Stabilizing
        to feed the magnetizing losses of all the CTs falling in                          resistor
        parallel and the relay pickup current, ISt. The sensitivity                       Relay
        of  the  differential  scheme  can therefore  be  expressed
        more appropriately  as


        (N being the number of  CTs falling in parallel) and in
        terms of the primary


        Since it determines the sensitivity level of the protection
        scheme, it must be kept as low as possible to detect even      L
                                                                        -G
        a small fault. To achieve a high degree of sensitivity it is   Relay-  High impedance single element ground fault
        therefore essential                                     differential protection relay

          To have the CTs with a low I,                Figure 15.29  Scheme for only ground fault differential protection
          To  keep  the  number  of  CTs  in  parallel  as  small  as
          possible, suggesting protection of individual feeders,
          rather than many feeders together, particularly when   In the case of overcurrent and ground fault protection
          the equipment is critical and requires a higher level of   it becomes much higher than in a single-pole relay. Now
          sensitivity for adequate protection.        the requirement of the minimum primary operating current,
                                                      Ipf (equation (lS.l)), which is a measure of sensitivity, is
          As the relay will have only one current setting for all   greatly reduced. The CT on the faulty phase has to feed
        types of faults, it is recommended to keep it around 20-   only  one third  of  the  CTs  that  fall in  parallel  of  each
        40% of  the rated current of  the machine or the system   relay coil rather than all the CTs, that fell in parallel in
        being protected. This setting will  be  sufficient to meet   ground fault protection using only a single-pole relay.
        the CT’s magnetizing current requirements and also trip   The CTs are designed for the worst conditions of fault,
        the relay.                                    even when the scheme is designed to detect only a ground
          For  a  ground  fault  scheme,  it  is  recommended  to   fault. This  may  be  a phase to phase and ground  fault,
        consider a still lower setting to ensure effective detection   causing a severe unbalance. The iron core of  such CTs
        of  the ground fault current and rapid disconnection  of   must  therefore  possess  near-linear  magnetizing
        the machine or the bus system being protected. A lower   characteristics,  to  the  extent  of  the  fault  level  of  the
        setting may be desirable as the actual ground fault current   machine or the system being protected. This is to achieve
        may already be larger than is being detected by the relay   a  near-replica  of  the  magnitude  of  the  fault  in  the
        due to a higher impedance of the ground loop than assumed   secondary, which may be 15 to 20 times or more of the
        previously.                                    rated current. In generators, it can increase to 21. I, (Section
          As a rule and as recommended by IEC 60255-6, the   13.4.1(5)). For the CTs, a saturation level sufficient to
        POC may be chosen within 30% of the minimum estimated   transform  the maximum primary  fault condition to the
        ground  fault  current. When  the  scheme  is  required  to   secondary is therefore considered  mandatory  to ensure
        detect only a ground fault, a single-pole relay is connected   that the CTs do not saturate during the most severe fault
        between all the CTs’ shorted ends (Figure 15.29). All the   condition, and render the tripping  scheme erratic. This
        CTs now fall in parallel.                      also ensures better stability of the relay, particularly during
          When the scheme is required to detect the ground fault   severe most through-fault conditions  (outside the CTs’
        as well  as the phase faults, a  triple-pole  relay  is used,   detection zone) such as a bus fault, as illustrated in Figure
        each pole  of  which  is  connected between  the  shorted   15.30. It is normal practice to define the secondary voltage
        terminals  of  the  two  same phase  CTs  and  the  neutral   of  the  CTs  by  its  knee  point  voltage  (kpv),  V,.  This
        formed by shorting the other terminals of all the CTs, as   voltage will depend upon the type of relay, its VA burden
        shown in  Figure  15.22. The setting  of  all the  poles  is   and the required  stability of  the  system. It  is common
        kept the same. In other words, the sensitivity level remains   practice to make this at least twice the relay setting voltage
        the same for all types of faults.              on the most severe through-fault, Le.  V,  2 2V,.
   505   506   507   508   509   510   511   512   513   514   515