Page 513 - Industrial Power Engineering and Applications Handbook
P. 513

Instrument and control transformers: application and selection  15/487
                                               R   Y  B









                                     Circuit breaker

























         characteristics








           Under healthy condition
               Figure 15.32  Phase and ground fault differential protection scheme for  a transformer and feeder bus protection


         Quantity = 6 numbers                          consequent spill currents to avoid an unwanted trip
              Vk  2  130 V
                                                           50 x lo3
              I,,,  = maximum  15 mA at a  Vk/2 of  65 V.   /  - -~
                                                          1.732xT1
         The  CT  manufacturer  must  provide  the  user  with  the
         magnetizing characteristics of  the CTs, i.e. I,,,  versus  V,.   = 2625 A
                                                       Consider a  reasonably  low  value  of  Ipf, say,  25%  of  I,,  to
         I1 Protection of a feeder circuit             achieve a high level of  sensitivity  and still feed the I,,,  to all
                                                       the
         Example 15.6                                  1 7 CTs
                                                          =
         Consider a  power  distribution system  as  shown  in  Figure   3
         15 32, where a transformer  of  50 MVA, 33/11 kV,  having a
        fault  level  of  750 MVA,  is  feeding a  bus connected to  six   ...  I,,  = 0.25 x 2625
        feeders of different ratings All the CTs for a combined phase   = 656.25 A
         and ground fault may be connected in parallel as illustrated
        The CTs on the primary side of the transformer will be similar   Assume the CTs on the secondary side of the transformer to
        to those on the  outgoing feeders,  except for the  insulation   be 3000/1 and on the primary to be
        system  and  the  turn  ratio,  to  provide  identical secondary
        current and magnetizing characteristics, as on the secondary   3000  11 or 1000 A
         side of  the transformer  The  relay may be set for  a slightly   1   33   1
         higher value to account for the slight error introduced and the   and their  magnetizing characteristics as in Figure 15.33.
   508   509   510   511   512   513   514   515   516   517   518