Page 610 - Industrial Power Engineering and Applications Handbook
P. 610

Voltage surges-causes,  effects and remedies  17/575
          OCB (MOCB or LOCB):                                    Entrance coil
                                                                 (suitable for a
          5 kV + 5.4 kV = 10.4 kV                               BIL of  (3p.u.16))
                   -~
           [l  P.U.  =  12
                     x 6.6 = 5.4 kV
          SF,  breaker: 7.5 kV + 5.4 kV = 12.9 kV
          Vacuum breaker with copper-chromium  contacts:
          6 kV + 5.4 kV = 11.4 kV
          Vacuum breaker with copper-bismuth  contacts:
          35 kV + 5.4 kV = 40.4 kV.
            From the  above  it  can be noted that the  surge voltages  -Jy vl= 3p.  .
          that may develop during a switching operation, with all types   Winding showing 6 slots or 6 coils per phase
          of breakers except Cu-Bi  VCBs, are well within the prescribed   and one turn per coil
          impulse withstand voltage of 16.2 kV as in Table 11.6, column   If, there be n number of turns per coil.
          2. In Cu-Bi  VCB  switching  it  may  be as  high as 40.4 kV,
                                                                                     Vt
          which is far beyond the prescribed impulse withstand level of   then voltage across each turn  =  -
          16.2 kV. Such breakers, as standard manufacturing practice,                6n
          are fitted with metal oxide surge arresters. Otherwise a suitable   Figure 17.16  One-phase winding, illustrating Influence of  the
          surge arrester must be provided near the motor.
                                                         arriving surge on the entrance coil
          17.8.2 Number of turns per coil
          This is another vital parameter of a machine, influencing   occurrence may gradually degrade its insulating strength to a
                                                         point of  a  possible  failure  over  a period of  time.  A  steep-
          the distribution of voltage surges over the windings. As   fronted  wave  may  damage  the  insulation  in  the  form  of
          noted  earlier, protection  of  interturn  insulation  is  very   microscopic  holes  called  'pinhole'  failures.  While  a  single
          important, particularly when  the  machine  has  a multi-   pinhole  may  be of  little  relevance,  a  number of  them  may
          turn  coil  arrangement  and where  the  turn  insulation is   cause hot spots, leading to eventual failure of the insulation.
          likely to be overstressed by the incident waves. Single-
          turn  coils. having the same turn and coil insulation and   17.8.3  Rating of a rotating machine
          coils deeper in the slots, are less influenced. A fast-rising
          voltage wave at the motor terminals will lift the potential   It  has been  seen  that  smaller rating  HT  machines  are
          of  the terminal  (entrance) turns,  while turns  deeper in   more susceptible to steeply rising voltage surges, compared
          the windings or the slots will be subjected to lesser severity   to larger ratings, due to their relatively weaker interturn
          due to discontinuities and partial reflections. They are,   insulation  and  require  more  careful  attention  to  their
          therefore, sluggish in responding to the arriving surges   adequate  protection.  We  attempt  to  explain  this
          and are subject to attenuated  severity of  the surge and   phenomenon  as follows:
          are less stressed than the entrance turns. To protect the
          line end coil or its first few turns. it is essential to keep   1  In  smaller  ratings  although  the  ratio  of  copper  to
          the length of the coil as short as possible, as illustrated in   insulation of the windings in the slot is low (the content
          Figure 17.14, to subject the whole coil to an equal interturn   of insulation high), the turn insulation is low, roughly
          stress.  Otherwise  the  severity of  the  surge may  affect
          only the entrance coil or its few entrance turns.
                                                        Table 17.1  Typical ratios of copper to insulation the turns per
                                                        coil in smaller frame sizes
          Example 17.3
          Consider  a  winding  having  six  numbers  of  coilslphase as   ~   ~   ~   ~   ~   ~   ~   ~~~   ~   ~   ~   ~
          shown in Figure 17.16, and suitable for a surge voltage (BIL)   Frame size  Ratio of  copper   Turns per- coil   Turn rnsulation
          of 3 p.u. (Table 11.6). If the surge travels only to the first coil,   (Table 1.2)  to insularion   to wlrclge
          which is suitable for 3/6 or 0.5 P.u., then all the effect of the   ~-    ~~   srtrgcs
                                                                 6.6 kV  11 kV
                                                                              6.6 kV  II kV
          surge (3 p.u) will impinge across this coil alone and greatly   -~ - - ~- -~
          overstress its interturn insulation. Thus, a 3 p.u. surge would   ~   ~   ~       ~~~
          stress the interturns by 3 p.u./0.5 p.u. or six times the voltage   400   1.5   0.8   12   20   Highly
          for which the insulation of the coil or its interturns are suitable            vulnerable
          or six times more than a uniformly distributed transient wave.   ~   - -~ - - -~  ~~   ~~   ~~~~   ~~   ~~~   ~~
          Hence, the relevance of  the length of  the entrance coil in a   5 00   2.0   1.2   9   15   Moderately
          steeply  rising voltage wave.                 630      2.2    1.3    6    IO   vulnerable
            Consequently an FOW, whose amplitude,  V,, is well below   ~~~   ~   -   ~~   ~~   ~~   ~~   ~~~   ~   ~-
                                                                    ~
          the insulation level (BIL) of the machine, may adversely affect   Note  For our discussion, the frame size 400 alone is more critical.
          the interturn insulation of the first coil. Even if the winding is   Frame  sizes  500  and  630  are  only  indicative to  illustrate the
          capable  of  withstanding  such  transients,  their  repeated   comparison.
   605   606   607   608   609   610   611   612   613   614   615