Page 612 - Industrial Power Engineering and Applications Handbook
P. 612

Voltage surges-causes,  effects and remedies  17/577
           0  The lower ratings of rotating machines, having full       ClGRE envelope
             load current of around 60 A and less, i.e. 600 kW     (based on the data obtained from
             or less for a 6.6 kV system and 300 kW or less for   a few manufacturers on a new winding)
             a  3.3  kV  system,  are  generally  prone  to  cause      /
             dangerous  steep-fronted TRVs  when  being  inter-
             rupted on no-load by a VCB or a vacuum contactor,
             as a result  of possible current chopping. For a full
             load current of 60 A, the no-load current would be
             approximately 50%, i.e. 30 A or even less (Section
             1.7). It is therefore possible that current chopping
             may take place just before a natural current zero at
             around  10% if  it,  i.e.  3 A  or so.  Refer  to  Figure
             17.17. The latest  vacuum interrupters with Cu-Cr
             alloy contacts (Section 19.5.6) may not allow the
             current  to  reach  its  natural  zero  for  a  normal
             interruption and may chop it somewhere near  3-5
             A and cause TRVs. Moreover, the lowest rating of   0   1   Front time (t,) ps -   6
                                                                                 4
                                                                                       5
                                                                            3
                                                                      2
             the interrupting device itself  may be  large enough
             for this current to be interrupted at current zero and
             cause current chopping.                      Figure 17.18  Dielectric envelopes for a 6.6 kV motor
         2  Transient  voltage  damage  usually  appears  in  some
           other  form  of  dielectric  failure  such  as  caused  by   Manufacturers  of  the  rotating  machines.  being  the
           thermal  overloading, undervoltage  and stalling etc.,   best judges, to suggest the most appropriate protection
           totally  masking  the  original  cause,  which  could  be   required for their machines, depending upon the surge
           due to switching. Field research and statistical study   impedance of the machine and the likely voltage surges
           of  failures  have  revealed  that  almost  35%  of  total   that may develop using different types of  switching
           dielectric  failures  in  power  stations  have  been   devices.
           caused by surges, rather than any other reason (Central
           Board of Irrigation and Power, 1995). Surge protection   Corollary
           for a smaller motor,  say, up to 300 kW  in a 3.3 kV   In case of static drives also generating similar switching
           and  600 kW  in  a  6.6 kV  system  is thus  advisable.   surges, their manufacturers provide the safe cable lengths
                                                       as a standard practice, Section 6.14.1.
                          v =  V,  sin wt
                                                       Dielectric envelope
                                                       This is a curve that defines the limits of  surge voltages
                                                       and the corresponding front times that a machine will be
                               0 95  vm   appearing across   able  to  sustain  without  a  failure  during  a  switching
                                       the contacts
                                                       operation  or  a  lightning  strike.  Such  a  curve  must  be
                                                       available  for  all  machines  and  is  provided  by  their
                                                       manufacturers. Figure 17. I8 shows a dielectric envelope
                                                       for  a  6.6  kV  motor  as  recommended  by  IEEE,  also
                                                       considering motor ageing. The figure also shows a curve
                                                       provided by  Electra (1981; see also Gibbs et (11..  1989).
                                                       This curve is based on the data obtained on new machines
                                                       from a few motor manufacturers.

                                                       Surge protection
                                                       Protection for the machine should be such that the voltage
                                                       surges and their  rise times, whenever they  occur in the
                                                       system, shall fall within  this envelope of  the machine.
                         V
           current chopping                            (Refer-  to Section  17.10 for a total  surge protection.)

                 time (of)           p.f = 0.3         17.9  Determining the severity of a
         i=O1  I,                    i$  = 72.54'            transient
                                     sin 72 54" = 0.95
         or  K!  I,                  :.  V, = 0.95  V,,,
            \2                                          17.9.1  Simulated test circuit
                  0.1
          :.   sin ot =  - and wf = 4.06'  and
                  1'2                                  From the above it is essential to predetermine the nature.
         TRV at current chopping = V,  sin 76.6"   0.97 V,   magnitude and steepness of such transients to decide the
         Figure  17.17  Current  chopping,  say,  at  10% of  an  inductive   most appropriate protection or preventive measures for
         current of 0.3 p.f. giving rise to almost a full system voltage.   an HT motor, particularly. for critical installations. such
   607   608   609   610   611   612   613   614   615   616   617