Starting of squirrel cage induction motors 4/71
          An  induction  motor can  be regarded  as a transformer   LT side thus eliminating the cause of a line disturbance
          with  a  small  air gap in  the  magnetic circuit. When  at   due to  a  voltage dip.  On  the  HT  side,  the  effect  of  a
          rest. having no induced back e.m.f., it can be regarded as   voltage  dip,  caused  by  small  motors,  is  of  little
          a transformer with a short-circuited secondary. A squirrel   significance.  However,  the  method  of  DOL  switching
          cage induction motor therefore draws a very high starting   for larger motors is recommended only where the supply
          current, as noted in  Section  1.2.1. However, it reduces   source has enough capacity to feed the starting kVA of
          substantially in a slip-ring motor due to the high impedance   the motor, with a voltage dip of not more than 59 on the
          of the rotor circuit.                          LT side.
            The starting of an induction motor does not relate to   For a large LT motor, say, 300 h.p.  and above, there is
          simple switching alone. It also involves its switchgears   no economical alternative other than DOL starting. One
          to control its starting inrush current, starting torque, or   can, however, employ delayed action coupling (Section
          both, and its overload and short-circuit protection.   8.3)  with  DOL  starting  to  start  the  motor  lightly  and
            The following are common methods to start a squirrel   quickly. (See also Example 7.1,  in  Chapter 7  for more
          cage motor, depending upon the limitation, if any, on the   clarity.). Soft starting through a solid-state device (Section
          magnitude of switching current, I,,.           6.16.1) or a liquid electrolyte (Section 4.2.3) are costly
                                                         propositions. Autotransformer starting is also expensive
                                                         due to the  cost  of  its  incoming  and outgoing control
          4.1  Direct on-line starting (DOL)             gears and the cost of the autotransformer itself. This is
                                                         also the case with  Y/A starting. Moreover, AIT and  Y/A
          This  is  an  ideal  type  of  starting,  and  is  simple and   startings are reduced voltage startings and influence the
          economical. In this type the full voltage is applied across   starting torque of the motor. It is possible that the reduced
          the stator windings. The torque developed by the motor   starting torque  may  not be  adequate to drive  the  load
          is  maximum. The  acceleration  is  fast  and  the  heat  of   successfully  and  within  the  thermal  withstand  time  of
          starting is low (Figure 4. I (a)). For heavy rotating masses,   the motor. Unlike in smaller ratings, where it is easy and
          with large moments of inertia, this is an ideal switching   economical  to obtain  a  high ir;, characteristic, in large
          method. The only limitation is the initial heavy inrush   motors, achieving a high T,,, say, 200% and above, may
          current, which may cause severe voltage disturbances to   be difficult  and uneconomical.  See Section 2.2.
          nearby feeders (due to a large I,, . Z drop). With this in   With the availability of large contactors up to 1000 A
          mind, even local electricity authorities sometimes restrict   and breakers up to 6400 A, DOL starting can be used for
          the use of DOL starting beyond a certain rating, say,  IO   LT  motors of any  size, say, up to  1000 h.p. The use of
          h.p., for small installations. For large installations, this   such  large  LT  motors  is,  however,  very  rare,  and  is
          condition may be of little significance as, in most cases,   generally  not  recommended.  Since  large  electrical
          the power from the electricity authorities may be available   installations  are  normally  fed  from  an  HT  network,
          on HT 3.3-33  kV. When it is so, a transformer is provided   whether it is an industry, residential housing, an office
          at the receiving end for the distribution of power on the   or a commercial  complex,  DOL switching. even  when








                                                                                         11 i_

                                                       t

                                                       c
                                                       f
                                                        3
                                                       0
                                                      I,     r-- -




                                                                                            h2
                                                                                                h3
                                       ______                                            3   On   Off
                              Speed +              N,                                  trip
                     (a) Torque and current characteristics       (b) Power and control circuit diagram
                                           Figure 4.1   Direct on-line starting