4/74  Industrial Power Engineering and Applications  Handbook

              R  Y  B  N















                                                                           i-


                                                                           ta








                                                                                  hl
                                                 1      1      1     1           1
                                                                                oic
                                                                                Trip
                           Notes
                           (1) C,  and C,  switches or contactors are interlocked among themselves, so that only one is ON at time.
                           (2)  C,  is essential to isolate the transformer after performing the starting duty, to eliminate avoidable transformer
               u  losses. Moreover the transformer is only short-time rated.
                0.4K
                                  Figure 4.4  Auto-transformer  starting (or 40% tapping)


                                                       kVA(,,,,   = continuous rating of the autotransformer.
                        .
         Tapping = 45 100%                      (4.1)
                                                         Since the transformer will be in the circuit for only 15
         From  this  equation,  the  desired  tapping  of  the  auto-   to 20 seconds, the approximate short-time rating of the
         transformer, to limit the starting current to a desired value   transformer  can  be  considered  to  be  10-15%  of  its
         can be determined.                            continuous  rating.  The  manufacturer  of  the  auto
                                                       transformer would be a better judge to suggest the most
                                                       appropriate rating of the transformer, based on the tapping
         Example 4.1                                   and starting period of the motor.
         A squirrel cage motor has its lSi on DOL as six times its rated
         current.  Find the required tapping on an autotransformer  to
         limit the starting current to 1.5 times.
                                                       Rating of contactors
                                                       Star contactor C, and AIT contactor C2 must be rated for
                                                       the  square of  the percentage tapping. For a  tapping  of
         or 50%                                        80%, for instance, the rating of the contactors Cl and C2
                                                       will be (0.Q2 or 64% of the full-load current of the motor.
         Rating of autotransformer                     The main  contactor  C,,  however,  will  be rated  for the
                                                       full-load current.
         Since an autotransformer is in the circuit for only a short   For power and control circuit diagrams refer to Figure
         period (during the start only), it can be short-time rated.   4.4.
         The rating of the autotransformer can be calculated from
         kVA (CMR,  = 43 . kV  ' I,,            (4.2)   Example 4.2
                                                       For a 3.3 kV 450 kW motor, with a full-load current of  100 A
         where                                         and starting current on DOL as six times the rated current,
              kV = applied voltage, and                the kVA rating of the transformer  for 50% tapping will be