Page 94 - Industrial Power Engineering and Applications Handbook
P. 94

Starting of squirrel cage induction motors  4/75
                  /AT  = 0.!j2 x 100 x 6 = 150 A from equation (4.1)   transients, in addition to causing current transients. The
                       -                                current transients may far exceed even  14-20  times the
          :.   kVA(CMR) = 43 x 3.3 x 150                rated current of the motor, as illustrated  in Figure 4.5,
                                                        depending  upon  the  transient  recovery  voltage  (TRV)
                    = 860 kVA                           (Section  17.6.2). We will describe the effect of an open
         An  autotransformer  of  nearly  100  kVA  continuously-rated   transient condition on an LT and HT machine separately.
         should be sufficient  for this application.
                                                        1  LT motors  In LT motors, such a situation may not
         Note  The above example is only for  a general  reference.   be a matter of concern as no switching surges  would
         The CDF of the transformer,  for the short-time rating, should
         be increased with the starting time and the number of starts   generally  occur. The voltage  would  be  too  low  to
         per hour.  Refer to the transformer  manufacturer for a more   cause a re-strike between the interrupting contacts of
         appropriate selection.                           the contactors (Section 17.7.6) and cause surges. The
                                                          motor's own induced e.m.f. may, however, fall phase
         4.2.2(a)  Open transient condition during a      apart with the applied voltage and the voltage across
                 reduced-voltage switching sequence       the motor windings may double. In all likelihood the
                                                          windings of  a motor would be  suitable to withstand
         Whenever a changeover of a switching device (contactors   effect of the same (Table 1 1.4). In locations, however,
         generally) from one condition to another takes place, as   that are humid or chemically contaminated, or where
         discussed above, in changing over from one tapping to   the motor is likely to be switched on after long gaps,
         another, as in an autotransformer switching, or from star   it is possible that the windings  may  have attained a
         to delta as in a Y/A switching, there appears a small time   low dielectric  strength to withstand a voltage up to
         gap of, say, 20-80 ms before the next contactor closes,   twice the rated one. Open transient conditions must
         after the first has dropped. During this period, while the   be avoided in all such cases.
         machine  will drop its  speed only very  marginally, and   2  HT Motors   Y/A switching  in  HT  motors  is  rare,
         which may not influence the load, the power from across   while an A/T switching may become necessary when
         the motor terminals will cease for this duration (except   the capacity of the feeding transformer is not adequate
          its own induced e.m.f.). This time gap, when switching   to withstand the start-up inrush of DOL switching, or
         HT motors particularly, may cause switching transients   when the drive calls for a frequent switching, such as
         and prove disastrous for the motor windings, as discussed   in a large compressor or pump house, and the feeding
          in  Section  17.7.2. This  is  termed  an  open  transient   transformer is not adequate for such a duty, or when
          condition. The situation is aggravated further because of   a number of  large drives are to be switched in quick
         the motor's  own  induced e.m.f., which  may  fall phase   succession  and the  feeding transformer  may  not  be
          apart with the applied voltage and magnify the voltage   adequate  to  sustain  such  heavy  inrush  currents.



                                                                 Note
                                                                  ob = Peak up to twice (=  14/J the actual /(A) current
                                                                     od  (it may even exceed 14-201,)
                                                                 ob, = No current transient during a closed transient
                                                                     switching
                                                                 c'c  = 1 to 2 ms. (opening + closing time of  Y and 3
             ISt(A)                                                  contactors respectively)
                                                                 Explanation:
                                                                  A. (i) ob is the current transient during changeover
                                                                     from  Y to  A  in an open transient condition.
                                                                   (ii) Voltage transient across the windings: 2.45 to
                                                 \  \                4.1 V,
            T                                      \             B. Sequence of a closed transient changeover,
                                                                    (i) When  the  bridging  resistor is introduced  in
            c
                                                                     parallel  to  Y  windings  at  point,  a, the  total
            E
           a                                                         impedance of the windings gets reduced and
                                                                     current has small overshoot to ob compared
                                                                     to its normal current, oa.
                                                                   (ii)There  is  no  voltage  transient  now  and  the
                                                                     voltage across the windings remains at  V,.
             lst(Y)                                                (iii) The Y contactor drops at bl, the impedance of
                                                                     the windings becomes high, current drops to
                                                                     9.
                                                         ..        (iv) The bridging resistor drops at b3 and the motor
                                                           $3  \  \   current traces back its normal A current curve
                                   Speed -                      1
                                                                     ~1 d.
                0                                      0        J8
                                Figure 4.5  Open and closed transient conditions  in YlA switching
   89   90   91   92   93   94   95   96   97   98   99