Starting of squirrel cage induction motors  4/73

                                                          R  Y  B  N
                                                          T  T  T  I


                                                        m
                                                        I
                                                        G


                                    I  Minimum  \ \                                           I
                                                        M
                                                       U
                                                       8


            I        Load torque    I          \\I
                           Speed -

                                  60%
                                                                                          O/COn  Off
                                                                                         trip
          Note  Current jumps to almost DOL current even at around 60%
         speed, if  switched to A position.

               (a) Torque-current characteristics on a  VA  starting


                                                        Motor windings in A
         Figure 4.3  Star-delta starting                         (b) Power and control circuit diagram




         3  This type of switching requires six cable leads to the   vulnerable  as  a  result  of  greatly  reduced  torque  and
            motor as against three for other types of switching to   necessitates a proper selection of  motor.
            accomplish the changeover of motor windings from Y
            to A.
                                                        To determine the tapping of  the autotransformer
         Ratings of contactors                          Consider an autotransformer with a tapping at 40%. Then
                                                        by equating the powers of the primary and the secondary
         Since all the contactors now fall in phase, they may be   sides of  the autotransformer (Figure 4.4)
         rated for the phase current only, i.e.  IrIa  58% of&
         The star contactor is in the circuit only for a short period
         and is generally chosen a size lower than the line and A
         conlactors.                                    or         I,,  = (0.4)'  .   V, IZ
           For power and control circuit diagrams refer to Figure
         4.3( b)  .                                     while the starting current on DOL:
                                                        I,,,   = 2:3  . V,IZ
                                                               7
         4.2.2  Autotransformer (AIT) starting
                                                        ... IAT  = (0.4)'  . IDOL
         For  smoother  acceleration  and to achieve a still lower
         starting current than above, this type of switching, although   i.e. proportional to the square of the tapping, where
         more expensive, may be employed. In this case also the   IAT = starting current on an autotransformer switching
         starting current and the torque are reduced  in a square   IDOL = starting current on a DOL switching
         proportion  of  the  tapping  of  the  autotransformer.  The   Z = impedance of the motor windings referred to the
         normal  tappings  of  an  autotransformer  are  40%, 60%   stator side per phase
         and 80%. At 40% tapping  the  starting  current and the
         starting torque will be only 16% that of DOL values. At   Generalizing the above equation, autotransformer tapping
         40%  tapping, therefore,  the  switching  becomes  highly   for a particular starting current, IAT is