Page 96 - Industrial Power Engineering and Applications Handbook
P. 96

Starting of  squirrel cage induction motors  4/77
        Table 4.1  Comparison between an open and a closed transient switching in terms of voltage and current

        Serial no.   Condition            Open transient               Closed transient
        ._ _-_____
         1         Voltage transient across the   Up to 3 to 5 p.u.  i.e. 3 to 5 (+)   There is no voltage transient. The voltage
                   motor windings                                     across the motor windings remain at ‘V;
                                          or 2.45 to 4.1Vr Section  17.7.2
        2          Current overshoot during   The current curve becomes a b c d   The current curve becomes ah,h,h,c,d
                   changeover  from Y to A,   (Figure 4.5) and current overshoots   (Figure 4.5). There is no current overshoot
                   point, a, on  Y current curve   from oa to ob momentarily, which   beyond the normal current in A
                   (Figure 4.5)           may exceed 14-201,
        _.                          __ _.   .-                                       .   .-
         ~
        Note  Since the surge impedance of a circuit is normally very high, as noted in Section 17.8, it is the voltage transient that is the cause of
        concern in the above case than the current transient.





                                                 I ’
                                        I
            fi-3L




















                                                                                            1
                                                                                            h3
                ~@                                         Control circuit        c         f
                                                                                  Trip
              Power circuit
                                                        c1 = Star contactor
                                                        C2 = Transformer contactor
                                                        C3 = Main contactor
                                                         d = Auxiliary contactor
                                                         T = Star connection-ON delay timer





                               Figure 4.7  Circuit diagram for a closed transition ATswitching
          reduced voltage. After the preset time of timer T the   4.2.3  Soft starting
          star contactor C1 falls out. The motor is still energized
          through the transformer  winding  without  any inter-   Soft  starting  minimizes  the  starting  mechanical  and
          ruption  during  the changeover. The main  contactor   thermal stressedshocks on the machine and the motor. It
           C, now energizes and the motor runs at full voltage.   results in reduced maintenance cost, fewer breakdowns
          The AIT contactor  C2 also falls out thus achieving a   and hence longer operating life for both. Reduced starting
          closed transient switching sequence.         current is an added advantage.
   91   92   93   94   95   96   97   98   99   100   101