Page 91 - Industrial Power Engineering and Applications Handbook
P. 91

4/72  Industrial Power Engineering and Applications  Handbook

        large LT motors  are used, may  not pose a problem  or
        cause any significant disturbance in the HT distribution
        network.  It  is, however,  advisable to employ  only  HT
        motors, in large ratings.
          HT motors have little alternative to be switched other
        than  a DOL or a  soft starting.  Y/A switching in  an HT
        motor is neither advisable nor possible for its windings
        are  normally  wound  in  a  star formation  to  reduce  the
        winding's  design voltage and economize on the cost of
        insulation.  Autotransformer  switching  is  possible,  but
        not used, to avoid a condition of open transient during a   (a) Line current   in case of  Y connected windings
        changeover  from one step  to  another,  as  discussed  in
        Section 4.2.2(a) and for economic reasons as noted above.
        Moreover, on a DOL in HT, the starting inrush current is
        not  very  high  as a  result of  low  full-load  current. For
        example, a 300 h.p. LT motor having a rated  full-load
        current (FLC) of 415 A  on a DOL will  have a starting
        inrush of approximately 2500 A, whereas a 3.3 kV motor
        will have an FLC of only 45 A and starting inrush on a
        DOL of only 275 A or so. An HT motor of  3.3, 6.6 or
        1 1 kV will thus create no disturbance to the HT distribution
        network on DOL starting.                       I-
          For power and control circuit diagrams refer to Figure
        4.1 (b).
                                                                        -_
                                                                          1
        4.2  Reduced voltage starting                                   -3
                                                                    or  I,  =  1  I,,
        When the power distribution network is available on LT,   (b) Line current IE2 in case of  A  connected windings
        and the motors are connected on such a system, it becomes        Figure 4.2
        dcsirable to reduce the starting inrush currents, for motors
        beyond a certain rating, say, 10 h.p., to avoid a large dip
        in the system voltage and an adverse influence on other   the motor has run to almost its full speed. Otherwise it
        loads connected on the same system. Sometimes it may   may  again  give  almost  a  full  kick  as  on  a  DOL and
        also be a  statutory requirement of the  local  electricity   defeat the purpose of  employing a staddelta switching.
        authorities for a consumer to limit the starting inrush of   Figure 4.3(a) explains this.
        motor currents beyond a certain h.p. to protect the system
        from disturbances. This requirement can be fulfilled by   Limitations
        adopting a reduced voltage starting.
          Sometimes the load itself may call for a soft start and   1  Due to the greatly reduced starting torque of the motor,
        a smoother acceleration and a reduced voltage switching   the accelerating torque also reduces even more sharply
        may become essential.                            and  severely  (Figure 4.3(a)).  Even  if  this  reduced
          A few common methods to achieve a reduced voltage   accelerating torque is adequate to accelerate the load,
        start are described below.                       it may take far too long to attain the rated speed. It
                                                         may even exceed the thermal  withstand capacity of
        4.2.1  Staddelta (Y/A) starting                  the motor and be detrimental to the life of the motor.
                                                         One considers this aspect when selecting this type of
        The use of this starting aims at limiting the starting inrush   switching.
        current, which is now only one third that of DOL starting.   To achieve the required performance, it is essential
        This is explained in Figure 4.2. This type of starting is,   that at every point on the motor speed-torque  curve
        however, suitable for only light loads, in view of a lower   the minimum available accelcrating torque is 15-20%
        torque, now developed by  the motor, which is also one   of its rated torque. In addition, the starting time must
        third that of  a DOL. If  load conditions  are severe, it is   also be less than  the thermal  withstand  time of  the
        likely that at certain points on the speed-torque  curve of   motor. For more details see Section 2.8.
        the motor the torque available may fall short of the load   2  This type of  switching is limited to only LT  system
        torque and the motor may stall. See the curves in Figure   for HT motors are normally wound in star. However,
        4.3(a), showing the variation in current and torque in the   in special cases, HT motors can also be designed for
        star and delta positions and the severe reduction  in the   delta at a higher cost to the insulation system which
        accelerating torque.                             may also call for a larger frame size. Also a provision
          When employing such a switching method precautions   can  be  made  in  the  switching  device  to  avoid  the
        should be taken or provision made in the starter to ensure   condition of an open transient during the changeover
        that the windings are switched ON to delta only when   from Y to A as discussed in Section 4.2.2(b).
   86   87   88   89   90   91   92   93   94   95   96