296   Instrumentation and control

                 compensating  resistor  is  incorporated  in  the  measuring  circuit.  The
                 insulating  plunger  varies  the  water flow in  order  to  correct  values to
                                                                        3
                 20®C  for  a convenient  measuring  unit, the  microsiemens/cm  or  dionic
                 unit.  A de-gassifier  should  be  fitted  upstream  of  this  unit  to  remove
                 dissolved  carbon  dioxide which  will cause errors in measurement.
                 Oxygen  analyser

                 The  measuring  of  oxygen  content  in  an  atmosphere  is  important,
                 particularly  when entering  enclosed  spaces.  Also  inert  gas systems use
                 exhaust  gases  which  must  be  monitored  to  ensure  that  their  oxygen
                 content  is below  5%. One  type of  instrument  used  to  measure  oxygen
                 content utilises the  fact that oxygen is attracted  by a magnetic field, that
                 is,  it is  paramagnetic.
                   A  measuring  cell  uses  a  dumb-bell  shaped  wire  which  rotates  in  a
                 magnetic  field.  The  presence  of  oxygen  will  affect  the  magnetic field
                 and  cause rotation  of the dumb-bell. The  current  required  to align the
                 dumb-bell  is a measure of the  oxygen  concentration  in the  cell.
                   The  sampling system for  an  inert  gas main is shown in Figure 15.22.
                 The  probe at the tap-off  point has an integral filter to remove dust. The


                              PRESSURE REGULATING
                                     VALVE

                                     VACUUM
                                     BREAK

                                 SEPARATOR





                                 XVALVE
                               C A LIBRA!
                   OXYGEN
                                  GAS
                   ANALYSER




                            | liiitllm



                               DRAIN
                 Figure  15.22 Oxygen  analyser