Page 328 - Introduction to Marine Engineering
P. 328

302  Instrumentation  and  control

                 the  transmitter  rotor  position, the  two e.m.f.s  will be out  of  balance. A
                 current  will flow and  the  receiver  rotor will turn  until it aligns with  the
                 transmitter. The  receiver  rotor  movement will  provide  a display of  the
                 measured  variable.
                   An  electrical  device  can  also be  used  as a transmitter  (Figure  15.28).
                 The  measured  variable  acts on  one  end  of  a  pivoted  beam  causing a
                 change in a magnetic circuit. The  change in the magnetic circuit results
                 in  a  change  in  output  current  from  the  oscillator  amplifier, and  the
                 oscillator output current operates  an electromagnet so that it produces a
                 negative  feedback  force  which  opposes  the  measured  variable change,
                 An  equilibrium position results and  provides an output signal


                 Hydraulic
                 The  telemotor  of a hydraulically actuated  steering  gear  is one example
                 of  a  hydraulic transmitter.  A complete description  of  the  unit  and  its
                 operation  is given in  Chapter  12.


                 Controller  action


                 The  transmitted output signal is received by the  controller  which must
                 then  undertake  some  corrective  action. There  will  however  be various
                 time  lags or  delays occurring during  first  the  measuring and  then  the
                 transmission of a signal indicating a change. A delay will also occur in the
                 action  of  the  controller.  These  delays  produce  what  is  known  as  the
                 transfer function of the unit or item, that is, the relationship between the
                 output and  input signals.
                   The  control  system is designed  to  maintain  some output  value at  a
                 constant desired  value, and  a knowledge of the various lags or  delays in
                 the  system  is  necessary  in  order  to  achieve the  desired  control.  The
                 controller  must therefore rapidly compensate for these system variations
                 and  ensure  a steady output  as near  to the  desired  value as  practicable.


                 Two-step  or on-off
                 In  this,  the  simplest of controller  actions, two extreme  positions  of  the
                 controller  are  possible,  either  on  or  off.  If  the  controller  were,  for
                 example, a valve it would be either  open  or  closed.  A heating system is
                 considered  with the control valve regulating the supply of heating steam.
                The  controller  action and  system response  is shown in  Figure  15.29. As
                the  measured  value  rises  above  its  desired  value  the  valve  will  close.
                System lags will result in a continuing temperature  rise which eventually
                 peaks and  then  falls  below the  desired  value. The  valve will then  open
   323   324   325   326   327   328   329   330   331   332   333