Effective use of heat pumps for various heating applications      115






















           Fig. 3.29 (A) Water-loop heat pump (WLHP) system; (B) 4-Tube fan-coil water heating,
           ventilation and air conditioning (HVAC) system. Q wl,ct, energy discharged, cooling tower;
           W p,wl , water loop pump consumption; W p,ct , cooling tower pump consumption; W f,ct, cooling
           tower fan consumption [18].





           Table 3.3 WLHP system: Annual energy consumption and mean efficiency parameters.
            WLHP system                     Madrid  Barcelona  Zaragoza  Porto

            Total thermal consumption (Q T ), kWh  7279.7  2443.3  6786.6  1751.6
            Total electrical consumption (W e , T ), kWh  12,974  13,550  14,729  10,140
            Heat pumps seasonal COP         4.05    4.07      4.05      4.08
            Heat pumps seasonal energy efficiency  3.82  3.82  3.82      3.82
              ratio (EER)
            Energy evacuated, cooling tower (Q wl,ct ),  46,337  55,287  54,400  41,553
              kWh
            Water loop pump consumption (W p , wl ),  335.2  362.9  383.7  272.5
              kWh
            Cooling tower pump consumption  362.5   432.5     425.6     325.1
              (W p , ct ), kWh
            Cooling tower fan consumption (W f , ct ),  318.8  434.0  405.2  300.6
              kWh
            Max. boiler power (P b , max ), kW  23.3  16.3    25.8      12.5
            Max. cooling tower dissipation rate  80.6  98.7   104.9     79.5
              (P ct , max ), kW