116                 Low-Temperature Energy Systems with Applications of Renewable Energy

         Table 3.4 4-Tube fan-coil system: Annual energy consumption and mean efficiency
         parameters.
          4-Tube fan-coil water system    Madrid  Barcelona  Zaragoza  Porto
          Total thermal consumption (Q T ), kWh  9876.3  3501.1  9332.3  2543.0
          Total electrical consumption (W e , T ), kWh  12,629  14,307  15,002  9856
          Chiller seasonal (EER)          3.23    3.38       3.20     3.67
          Heating circuit pump consumption  19.6  6.9        18.5     5.0
            (W p , b ), kWh
          Cooling circuit pump consumption  230.6  275.2     271.0    206.9
            (W p , ch ), kWh
          Dry condenser fan consumption (W f , dc ),  969.1  1004.0  1163.8  641.1
            kWh
          Max. boiler power (P b , max ), kW  32.6  22.8     36.1     17.4
          Max. chiller cooling rate (P ch , max ), kW  22.8  24.8  29.3  21.8




            The choice of WLHPS is determined by climatic conditions. In southern latitudes,
         air cooling is effectively provided by a chiller-fancoil system. In the northern latitudes
         a bivalent system is applied more effectively. In a temperate climate of middle lati-
         tudes, it is advisable to use a WLHPS. However, whether a WLHPS is appropriate
         or not for any project will be determined by a feasibility study that accounts for tech-
         nical and economic considerations [20].