Page 406 - Mechanical Engineers' Handbook (Volume 4)
P. 406

2 Heat-Transfer Correlations for Electronic Equipment Cooling  395

                                                            σ       σ 2
                                                             1  TIM      Material 2







                                                Material 1




                                                                Bulk
                                                              resistance
                                                                           2
                                                                       k contact =  k + k 2 k k TIM TIM
                                                                           2
                                                                k TIM
                                                      2
                                                  k contact =  k + k 1 k k TIM  BLT
                                                        TIM
                                                      1
                                         Temperature

                                                                   Distance

                                                Contact
                                              resistance
                                       Figure 11 Schematic showing temperature drop across an interface.


            2.4  Forced Convection
                           External Flow on a Plane Surface
                           For an unheated starting length of the plane surface, x , in laminar flow, the local Nusselt
                                                                      0
                           number can be expressed by
                                                            0.332Re 1/2 Pr 1 /3
                                                     Nu                                         (54)
                                                       x            3/4 1 /3
                                                           [1   (x /x)  ]
                                                                 0
                           Where Re is the Reynolds number, Pr is the Prandtl number, and Nu is the Nusselt number.
                              For flow in the inlet zones of parallel plate channels and along isolated plates, the heat-
                                                                                   3
                           transfer coefficient varies with L, the distance from the leading edge. in the range Re
                                 5
                           3   10 ,
                                                    h   0.664       0.5  0.33
                                                              k
                                                               fl
                                                              L   Re Pr                         (55)
                           and for Re   3   10 5
                                                    h   0.036       0.8  0.33
                                                              k
                                                               fl
                                                              L   Re Pr                         (56)
                           Cylinders in Cross-flow
                           For airflow around single cylinders at all but very low Reynolds numbers, Hilpert 23  has
                           proposed
   401   402   403   404   405   406   407   408   409   410   411