Page 180 - Pipeline Rules of Thumb Handbook
P. 180

Control Valves  167

                                 Table 1                         verted to a K factor by using Figure 2. In this case, 6-in. K v
                                                                 is 0.05.
                                                                   Pipe resistance must also be considered (Figure 5). The
                                                                 L/D ratio must be calculated with reference to the same units
                                                                 of L and D. In the example, 12ft of 6-in. pipe has a K p equal
                                                                 to 0.36.
                                                                   All resistances must be converted to the same base diam-
                                                                 eter (in this case 6in.). The entrance factor, K e is 0.05 for 12-
                                                                 in. Referring to Figure 6, the 6-in. K e is about 0.04; the 12-in.
                                                                 elbow coefficient converted to 6-in., 6-in. K el is 0.02, and the
                                                                 12-in. exit coefficient, 6-in. K x , is 0.8. A tabulation and sum of
                                                                 these coefficients as determined from Figure 3 would be:

             All K factors, L/D’s or C v ’s must be converted to the same  12≤ Entrance  6≤ K e = 0.04
           basis using the same diameter d when using an over-all C v for  6≤ Reducer—Increaser  6≤ K ri = 0.80
           a piping run. This can be accomplished with the following  2–6≤ Valves        6≤ K v = 0.10
           equations:                                             6≤ Control Valve       6≤ K v = 10.00
                                                                 12-ft spool of 6≤ Pipe  6≤ K p = 0.36
                             4
                 b (
           K a =  K f f b )( d d b )                       (8)   12≤ Elbow               6≤ K el = 0.02
                   a
                         a
                                                                 12≤ Exit                6≤ K x = 0.08
                               4
           ( LD) = ( LD) ( d d b )                         (9)                             SK = 11.40
                a       b  a
           ( ) = ( ) ( d d a ) 2                          (10)     Refer to Figure 2 for a conversion of K to C v . With the
                        b
           C v a
                  C v b
                                                                 above values noted, the overall 6-in. C v is 320, approximately
                                                                 a 6% reduction of the original C v of 340.
                               Examples                            Now refer to Figure 4. This is an identical control valve
                                                                 run with Figure 3, except that a 6-in.  ¥ 4-in.  ¥ 6-in. high-
             Refer to Figure 3 for a schematic of a typical control valve  capacity ball valve has been substituted for the 6-in. single-
           station using an old style control valve. Flow is from a header  ported globe body control valve. Note that the SK now is 1.93,
           through a 12-in. by 6-in. reducer, a 6-in. isolating valve, 6-in.  which converted to an overall C v is 775. This is a reduction of
           globe body control valve, 6-in. pipe spool, a second isolating  about 48% from the original 6-in. ¥ 4-in. ¥ 6-in. control valve
           valve, a 6-in. by 12-in. increaser, a 12-in. welding elbow and  C v of 1,495.
           into a header. Note should be made of Figure 1 in that the  If in Figure 4, the 6-in. ¥ 4-in. ¥ 6-in. valve were substi-
           C v from the solid curve is for the complete reducer-increaser  tuted with a full open 6-in. ball valve, the overall C v is 895.
           combination with regard to the ratio of diameters. In this case,  This represents a reduction in C v of about 81% from the orig-
           the Beta ratio is 6/12 or 0.5 and C v is 1,200 for the small diam-  inal 6-in. ball valve C v of 4,700.
           eter of 6-in. Since C v ’s cannot be simply added, they must be  The methods and graphs presented in this article are pro-
           converted to K factors. To do this, refer to Figure 2, which  posed for sizing and calculating pressure drops in a control
           converts C v to K.                                    station. The assumption of assigning values to certain un-
             Also to be considered are the isolating valves and control  usual piping configuration must be recognized. The author
           valves. Resistance coefficients, C v ’s or pressure drop factors  has some field data confirmation on similar control station
           are published by most valve manufacturers and may be con-  designs.
















                       Figure 3. Piping configuration.                        Figure 4. Piping configuration.
   175   176   177   178   179   180   181   182   183   184   185