Page 182 - Pipeline Rules of Thumb Handbook
P. 182

Control Valves  169

           Control valve selection


             A control valve may be thought of as a section of pipe with               Table 1
           a variable resistance. Control valves are typically used to   Typical Values of C v for Control Valves*
           match pumps to the pipeline system characteristics. They are        (Equal Percentage Trim)
           not normally used with reciprocating compressors but may be
                                                                               Double       Single
           used with centrifugal compressors for preventing surge.
                                                                    Valve      Ported      Ported      Ball Valve
             Liquid pipeline applications usually involve controlling the                                      †
                                                                     Size      Globe        Globe      Full Bore
           flow rate, suction and discharge pressure, and other variables
           for centrifugal pumps. Control valves may also be used with  2         48          46            406
           reciprocating pumps to regulate the pump discharge pressure  4        195         195          1,890
           by recycling fluid from the pump discharge to the pump      6          450         400          4,580
           suction when the discharge pressure approaches the control  8         750         640          8,900
           point. The control valve may also be used to unload the pump  10     1,160       1,000        14,600
           during the start-up by opening just prior to start-up and slowly  12  1,620                   22,800
           closing after the pump driver is up to operating speed.   14         2,000                    28,700
                                                                     16         2,560                    38,900
             Other applications for control valves include:
                                                                     20                                  66,000
                                                                     24                                  98,600
            • Pressure reduction                                     26                                 119,800
            • Pressure relief
            • Back pressure control                              * These values are suitable for estimating only. The valve manufacturer
            • Control delivery flow rates                          should be consulted for the actual C v for the valve selected.
                                                                 †  Courtesy: Thunderco—Houston.
             Ideally, the pump(s) for a system will be sized such that a
           minimum amount of pressure throttling will be required
           during normal operations. System startup, system upsets, and
           unit startup and shutdown require that a means be provided
           to regulate pressures, flow rates, and in some cases motor
           load. This may be accomplished by using variable speed
           motors, variable speed couplings, or a control valve.
             The control valve, when used with centrifugal pumping
           units, is installed in the pump discharge line. If multiple
           pumping units are used, only one control valve will be
           required.
             Table 1 lists typical values of C v for conventional and ball
           control valves.
             When conventional globe-type control valves are used in
           pipeline applications for pump control, valves with equal per-
           centage trim are the best choice. Figure 1 shows the typical
           control valve static characteristic curves for quick opening,
           linear, and equal-percentage valve trims.
             Curves such as those shown in Figure 1 are based on main-
           taining a constant differential pressure of 1psig across the
           valve for varying flow rates. In actual practice, the pressure  Figure 1. Control valve characteristics.
           differential across the control valve will vary according to the
           needs of the system. Figure 2 shows a comparison of the static
           and dynamic characteristics for an equal percentage control
           valve. The dynamic characteristic curve was developed by  to calculate the pressure loss in the pipeline. The pressure
           taking the pressure drop across a 12-in. double-ported valve  drop across the control valve was calculated for various flow
           with equal percentage trim in series with ten miles of 12-in.  rates while maintaining a constant system input pressure. The
           pipeline. A maximum flow rate of 6,000bbl/hr of 0.86 sp. gr.  C v was then calculated for each of the flow conditions and
           crude oil at a constant input pressure of 1,000psig was used  converted to percent of valve lift.
   177   178   179   180   181   182   183   184   185   186   187