Page 148 - Power Electronic Control in Electrical Systems
P. 148

//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH004.3D ± 136 ± [106±152/47] 17.11.2001 9:54AM







               136 Power flows in compensation and control studies

                      The linearized SVC equation is given below, where the variable susceptance B SVC is
                      taken to be the state variable
                                                        0  0
                                              P l                 y l
                                                   ˆ      @Q l                          (4:66)
                                              Q l     0          B SVC
                                                         @B SVC
                      At the end of iteration (r), the variable shunt susceptance B SVC is updated
                                               B (r ‡ 1)  ˆ B (r)  ‡  B (r)             (4:67)
                                                 SVC    SVC      SVC
                      4.5.3  Numerical example 5

                      The five-node network detailed in Section 4.4.6 is modified to include one SVC
                      connected at node Lake to maintain the nodal voltage magnitude at 1 p.u. Conver-
                      gence is obtained in four iterations to a power mismatch tolerance of e   10  12  using
                      an OOP Newton±Raphson power flow program (Fuerte-Esquivel et al., 1988). The
                      power flow solution is shown in Figure 4.18 whereas the nodal voltage magnitudes
                      and phase angles are given in Table 4.5.
                        The power flow result indicates that the SVC generates 20.5 MVAr in order to
                      keep the voltage magnitude at 1 p.u. voltage magnitude at Lake node. The SVC
                      installation results in an improved network voltage profile except in Elm, which is
                      too far away from Lake node to benefit from the SVC influence.
                        The Slack generator reduces its reactive power generation by almost 6% compared
                      to the base case and the reactive power exported from North to Lake reduces by
                      more than 30%. The largest reactive power flow takes place in the transmission line
                      connecting North and South, where 74.1 MVAr leaves North and 74 MVAr arrives
                      at South. In general, more reactive power is available in the network than in the base
                      case and the generator connected at South increases its share of reactive power




























                      Fig. 4.18 SVC upgraded test networkand power flow results.
   143   144   145   146   147   148   149   150   151   152   153