Page 152 - Power Electronic Control in Electrical Systems
P. 152

//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH004.3D ± 140 ± [106±152/47] 17.11.2001 9:54AM







               140 Power flows in compensation and control studies

                        For the case when the TCSC is controlling active power flowing from nodes l to m
                      at a value P reg  the set of linearized power flow equations are
                                lm
                                            2                         3
                                              @P l  @P l  @P l  @P l  @P l
                                 2      3                               2       3
                                              @y l  @y m  @jV l j  @jV m j  @X TCSC
                                    P l                                     y l
                                             @P m  @P m  @P m  @P m
                                            6                         7
                                            6                     @P m 7
                                 6   P m  7   @y l  @y m  @jV l j  @jV m j  6   y m  7
                                            6                    @X TCSC 7
                                 6      7                               6       7
                                             @Q l  @Q l  @Q l  @Q l
                                            6                     @Q l 7
                                 6   Q l  7                             6   jV l j  7   (4:78)
                                              @y l  @y m  @jV l j  @jV m j  7
                                         ˆ 6
                                 6      7                        @X TCSC 6      7
                                            6                         7
                                 4   Q m  5  @Q m  @Q m  @Q m  @Q m     4   jV m j  5
                                            6                     @Q m 7
                                              @y l  @y m  @jV l j  @jV m j
                                            4                    @X TCSC 5
                                    P lm                                  X TCSC
                                             @P lm  @P lm  @P lm  @P lm  @P lm
                                              @y l  @y m  @jV l j  @jV m j  @X TCSC
                      The active power flow mismatch equation in the TCSC is,
                                                  P lm ˆ P reg    P calc                (4:79)
                                                          lm   lm
                      and the state variable X TCSC of the series controller is updated at the end of iteration
                      (r) using the following equation
                                                                 (r)
                                                        (r)
                                              X (r ‡ 1)  ˆ X TCSC  ‡  X TCSC            (4:80)
                                                TCSC
                      4.6.3  Numerical example 6
                      The original network has been modified to include one TCSC to compensate the
                      transmission line connecting nodes Lake and Main. The TCSC is used to maintain
                      active power flow towards Main at 21 MW. The initial condition of the TCSC is set
                      at 50% of the transmission line inductive reactance given in Table 4.2, i.e. X ˆ 1:5%.
                      Convergence was obtained in five iterations to a power mismatch tolerance of
                      e   10  12 . The power flow results are shown on Figure 4.20 and the nodal voltage
                      magnitudes and phase angles are given in Table 4.6.
                        Since the TCSC cannot generate active power, there is an increase in active power
                      flowing towards Lake node, through the transmission lines connecting North to
                      Lake and South to Lake, in order to meet the increase in active power specified at
                      the sending end of the TCSC. In the transmission line South±Lake, the active power
                      flow increases from 24.47 MW in the original network to 25.5 MW at the sending end
                      of the line whereas in the transmission line North±Lake, the increase is from
                      41.79 MW to 42.43 MW.
                        It should be remarked that transmission line Lake±Main was series compensated to
                      increase the active power flow from 19.38 MW to 21MW, which is just under 8% active
                      power increase. The nodal voltage magnitudes do not change compared to the base case
                      but the voltage phase angles do change; particularly at Lake node where there is a
                      negative increase of almost one degree to enable increases in active power flows.
                      4.6.4 SPS power flow modelling

                      TheactiveandreactivepowersinjectedatnodeslandmbytheSPSshowninFigure4.3are

                                       2
                                P l ˆjV l j G ll ‡jV l jjV m j(G lm cos (y l   y m ) ‡ B lm sin (y l   y m ))  (4:81)
                                      2
                             Q l ˆ jV l j B ll  jV l jjV m j(B lm cos (y l   y m )   G lm sin (y l   y m ))  (4:82)
   147   148   149   150   151   152   153   154   155   156   157