Page 154 - Power Electronic Control in Electrical Systems
P. 154

//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH004.3D ± 142 ± [106±152/47] 17.11.2001 9:54AM







               142 Power flows in compensation and control studies

                        It should be pointed out that the SPS in Figure 4.3(b) has the phase angle tapping
                      in the primary winding and that its effect may be incorporated in the phase angle y m .
                      Hence, the Jacobian terms corresponding to P l , Q l , P m and Q m are derived with
                      respect to y m , as opposed to f, using equations (4.81)±(4.82). For cases when the
                      phase shifter angle is in the secondary winding the corresponding Jacobian terms are
                      derived with respect to y l .
                        The state variable f is updated at the end of iteration (r) using the following equation
                                                 f (r ‡ 1)  ˆ f (r)  ‡  f (r)           (4:85)


                      4.6.5  Numerical example 7
                      The original network is modified to include one SPS to control active power flow in
                      the transmission line connecting nodes Lake and Main. The SPS is used to maintain
                      active power flow towards Main at 40 MW. The SPS reactance is 10% and the initial

                      condition for the phase shifting angle is 0 . The actual phase shifting angle required
                      to keep active power flow at 40 MW is  5:83 . Convergence is obtained in four

                      iterations to a power mismatch tolerance of e   10  12 . The power flow results are
                      shown on Figure 4.21 and the nodal voltage magnitudes and phase angles are given
                      in Table 4.7.
                        Since the SPS cannot generate active power, there is a large increase in active
                      power, compared to the base case, flowing towards Lake node through the transmis-
                      sion lines connecting North to Lake and South to Lake. In the transmission line
                      North±Lake, the active power flow increases from 41.79 MW to 50.3 MW at the
                      sending end of the line whereas in the transmission line South±Lake, the increase is
                      from 24.47 MW to 37.6 MW.






























                      Fig. 4.21 SPS upgraded test networkand power flow results.
   149   150   151   152   153   154   155   156   157   158   159