Page 160 - Power Electronic Control in Electrical Systems
P. 160

//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH004.3D ± 148 ± [106±152/47] 17.11.2001 9:54AM







               148 Power flows in compensation and control studies

                      Table 4.9 Nodal complex voltages of UPFC upgraded network
                      Voltage                                System nodes
                      information
                                      North        South       Lake        Main         Elm
                      jVj (p.u.)      1.06          1           1            0.992        0.975
                      y (degrees)     0             1.77        6.02        3.19         5.77


                      active power flow have taken place, particularly in the powers flowing towards Lake
                      node through transmission lines connected between North±Lake and South±Lake.
                      The resulting power flows satisfy the power consumed by the load at Lake node
                      (45 MW) and the active power demanded by the UPFC series converter, which is set
                      to control active power flow at 40 MW as opposed to the 19.38 MW that existed in
                      the original network. The maximum amount of active power exchanged between the
                      UPFC and the AC system will depend on the robustness of the UPFC shunt node,
                      i.e. Lake node. Since the UPFC generates its own reactive power, the generator
                      connected at North node decreases its reactive power generation and the generator
                      connected at South node increases its absorption of reactive power.
                        As a further exercise, we look at the characteristics of the DVR as a steady state
                      controller. The UPFC model is replaced with a DVR model and the complex
                      voltages are shown in Table 4.10.
                        The Newton±Raphson algorithm converges in five iterations to a mismatch power
                      tolerance of e   10  12 . The DVR also controls active and reactive power flows
                      through transmission line Lake±Main at 40 MW and 2 MVAr, respectively. The
                      voltage magnitude and phase angle of the series voltage source are: jV cR jˆ































                      Fig. 4.23 UPFC upgraded test networkand power flow results.
   155   156   157   158   159   160   161   162   163   164   165