Page 289 - Power Electronic Control in Electrical Systems
P. 289

//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH007.3D ± 277 ± [263±289/27] 17.11.2001 10:25AM







                                                            Power electronic control in electrical systems 277

                      connected TCR does not prevent completely the third harmonic currents and their
                      multiples from reaching the network. It should be remarked that under balanced
                      operation, these harmonic currents should be confined within the delta connected
                      circuit. Also, as expected, TCR currents above the 13th harmonic term are quite
                      small and may be ignored in most network harmonic studies.
                        Sometimes it is useful to use simplified expressions to check the sanity of the
                      results. In this case, we shall calculate the fundamental frequency, positive sequence
                      component of the TCR current by using the following equation (Miller, 1982)
                                                   (s   sin s) V
                                              I 1 ˆ             A rms                    (7:37)
                                                       p     X L
                      which gives the following result
                                               p   )   sin 120     3
                                       (120    180          33   10
                                   I 1 ˆ                       p   ˆ 263:48 A rms     (7:38)
                                         p(2p   50   0:09)      3
                        This value agrees rather well with the positive sequence value derived from apply-
                      ing symmetrical components to the fundamental frequency three-phase currents
                      given in Table 7.1, i.e. 263.47 A rms.

                      7.4.3.2 Numerical example 3
                      A portion of a 220-kVpower system for which complete information exists in the
                      open literature (Acha et al., 1989) is used to illustrate the results produced by the
                      three-phase TCR model. The system is shown in Figure 7.7. This is a well-studied test
                      network, which shows a parallel resonance laying between the 4th and 5th harmonic
                      frequencies, i.e. 200±250 Hz, as shown by the frequency response impedance in
                      Figure 7.8.
                        A delta connected three-phase TCR is connected at busbar 1. Transmission lines
                      are modelled with full frequency-dependence, geometric imbalances and long-line
                      effects. Generators, transformers and loads have been assumed to behave linearly.

























                      Fig. 7.7 Test system.
   284   285   286   287   288   289   290   291   292   293   294