Page 76 - Power Electronic Control in Electrical Systems
P. 76

//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH002.3D ± 65 ± [31±81/51] 17.11.2001 9:49AM







                                                             Power electronic control in electrical systems 65

                      current, and core losses; but these can be neglected when considering many of the
                      main functions of transformers. 12
                        The impedance `looking into' the transformer at the primary terminals is the ratio
                                                                       2
                      V 1 /I 1 , and from equation (2.43) this is equal to (N 1 /N 2 ) Z L , where Z L is the load
                      impedance connected on the secondary side. This is called the `referred' impedance,
                        0
                      Z . If the primary side has a higher voltage than the secondary side, i.e. N 1 /N 2 > 1,
                        L
                            0
                      then Z will be larger than Z L . For example, in an 11 kV/415 V transformer the
                            L
                                                 2
                      impedance ratio is (11 000/415) ˆ 702:5.
                      2.11.2   Functions
                      Transformers have several functions in power transmission and distribution, for
                      example:
                      (a) transform voltage level for optimum transmission
                      (b) isolate coupled circuits
                      (c) impedance matching
                      (d) introduce series impedance (to limit fault current)
                      (e) create a neutral point (e.g. ground connection remote from power station)
                      (f ) suppress harmonics (especially triplen harmonics)
                      (g) provide tappings for loads along a tranmission line
                      (h) produce phase shift or multiple phases (e.g. for multiple-pulse converters)
                      (i) frequency-multiplication (saturated core)
                      (j) constant-voltage reactive compensation (saturated core).
                      Three-phase transformers are often wound on common cores such as the one shown
                      in Figure 2.38. The windings on both sides may be connected in wye or delta, giving





















                      Fig. 2.38 Unwound 3-limb transformer core.


                      12
                        These `imperfections' can usually be included in calculations by means of additional parasitic im-
                      pedances added to the equivalent circuit of Figure 2.37. One of the most important of these impedances
                      is the leakage reactance which represents the imperfect magnetic coupling between the primary and
                      secondary windings and appears as a series reactance either in the primary or secondary circuit, or shared
                      between them.
   71   72   73   74   75   76   77   78   79   80   81