Page 81 - Power Electronic Control in Electrical Systems
P. 81

//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH002.3D ± 70 ± [31±81/51] 17.11.2001 9:49AM







               70 Power systems engineering ± fundamental concepts

                        Now define the per-unit complex powerss 1 ˆ S 1 /S 1b and s 2 ˆ S 2 /S 2b where `b' means
                                                    15
                      the `base' MVA for each transformer. Also, the per-unit impedances are defined as
                                         Z 1       S 1b           Z 2       S 2b
                                    z 1 ˆ   ˆ Z 1    2  and  z 2 ˆ   ˆ Z 2    2         (2:53)
                                        Z 1b       V             Z 2b       V
                                                    1b                       2b
                      so that
                                          s 1  S 1 =S 1b  Z   2  S 2b  z   2  V 2 2b
                                             ˆ       ˆ         ˆ       2                (2:54)
                                          s 2  S 2 =S 2b  Z    S 1b  z    V
                                                         1        1    1b
                      If V 1b is chosen to be equal to V 2b , then
                                                           z
                                                      s 1   2
                                                         ˆ                              (2:55)
                                                      s 2  z
                                                            1
                      If the transformers are to be loaded in proportion to their ratings, then s 1 ˆ s 2 ,which
                      requires that z 1 ˆ z 2 . That is, the per-unit impedances of the transformers must be
                      equal, when evaluated on their own respective MVA bases and a common voltage base.
                        When three-phase transformers are connected in parallel, the requirement for
                      `correct polarity' is slightly more complicated. The phase shift between correspond-
                      ing primary and secondary voltages must be the same in both transformers. This
                      means that both transformers must belong to the same group. For example, a Yy0
                      transformer can be paralleled with a Dd0 transformer, because the phase shift is zero
                      through both of them. But a Yd1 cannot be paralleled with a Yy0, because the Yd1
                      has a phase shift of  30 .

                      2.11.4   Zero-sequence effects in three-phase transformers

                      In normal operation of a three-phase system, the voltages and currents are balanced
                      and

                                                   I a ‡ I b ‡ I c ˆ 0                  (2:56)
                      This equation is satisfied not only by the line currents, but also by the line-neutral
                      voltages and the line±line voltages in balanced operation.
                        In a transformer core the voltages establish fluxes in the core. If each phase
                      winding has the same number of turns on each limb of the core, then the limb fluxes
                      will also be balanced: i.e.,
                                                  F a ‡ F b ‡ F c ˆ 0                   (2:57)
                      In balanced operation, the flux through any limb at any instant is returning through
                      the other two limbs, so there is no tendency for flux to leakoutside the three limbs.
                      (Figure 2.44).
                        If the operation is unbalanced there may be a `residual' current, I 0 ˆ I a ‡ I b ‡ I c ,
                      and/or a residual voltage V 0 ˆ V a ‡ V b ‡ V c , and a residual flux F 0 ˆ F a ‡ F b ‡ F c .
                      These residual quantities are also called `zero-sequence' quantities. 16  Zero-sequence
                      components are all in phase with each other. Unlike positive/negative-sequence


                      15
                       See x2:13.
   76   77   78   79   80   81   82   83   84   85   86