Page 108 - Power Quality in Electrical Systems
P. 108

Power Harmonic Filters  91


         120 A

          80 A
          40 A

           0 A

         −40 A
         −80 A

        −120 A
           300 ms 310 ms 320 ms 330 ms 340 ms 350 ms  360 ms 370 ms  380 ms 390 ms 400 ms
               i(ls)                    Time
                                         (b)

        120 A

        100 A

         80 A

         60 A

         40 A
         20 A

          0 A
            0 Hz 0.1 KHz 0.2 KHz 0.3 KHz 0.4 KHz 0.5 KHz  0.6 KHz 0.7 KHz  0.8 KHz 0.9 KHz 1.0 KHz
              i(Ls)                   Frequency
                                         (c)
        Figure 6.17 (Continued)



        TABLE 6.1 Harmonic Currents for
        Example 6.1
         Harmonic number  Value (Amps)
               1             100
               5              50
               7              25
              11              15
   103   104   105   106   107   108   109   110   111   112   113