Page 106 - Power Quality in Electrical Systems
P. 106

Power Harmonic Filters  89


                     Ls                                      PCC
                    100 uH          I L        1 5      1 7
           v s  +  j(37.7 mΩ)      +          +        + −
              −
                                   −
                                              −
        277 V                        100 A     20 A      15 A
                                   (a)

         120 A
          80 A

          40 A

           0 A
         −40 A

         −80 A

        −120 A
             10 s  10 ms 20 ms 30 ms 40 ms 50 ms  60 ms 70 ms  80 ms 90 ms 100 ms
               I(Ls)                    Time
                                         (b)

        120 A

        100 A
         80 A

         60 A

         40 A
         20 A

          0 A
            0Hz 0.1KHz 0.2KHz 0.3KHz 0.4KHz 0.5KHz  0.6KHz 0.7KHz  0.8KHz 0.9KHz 1.0KHz
               I(Ls)                  Frequency
                                         (c)
        Figure 6.16 The circuit for Example 6.2. (a) The circuit. (b) The line current. (c) The spec-
        trum of the line current.

          First, we need to determine what the IEEE-519 limits are for line har-
        monic currents, using Table 10.3 (Figure 6.5). Note that the harmonic
        current limits depend on the ratio I /I , where I SC  is the short-circuit
                                             L
                                         SC
        current at the PCC, and I   100 A is the fundamental load current. For
                               L
   101   102   103   104   105   106   107   108   109   110   111