Page 140 - Power Quality in Electrical Systems
P. 140

122    Chapter Eight


              A
        Source B
              C

                          a1                 Load  Load  Load

                          a2                               3d harmonic
                                                             currents
                     c2
                c1        b2
                             b1



              N
                     Transformer
        Figure 8.12  A third harmonic grounding transformer.




        is the grounding transformer shown in Figure 8.12 [8.12], which is
        located close to a collection of single-phase loads that produce 3d-har-
        monic currents. The third-harmonic currents are prevented from trav-
        eling back to the source in the neutral conductor.
          The constant voltage transformer (CVT) utilizes a leakage-reac-
        tance transformer with a saturable magnetic core and a capacitor to
        obtain relatively constant output voltage in the face of input voltage
        sags down to a remaining voltage of 70 percent at full load and to 30 per-
        cent at a 25 percent load. The characteristic curves for time in cycles
        and percent load are shown in Figure 8.13 [8.13]. The response occurs
        within a half cycle and is not limited in time. The transformers are rel-
        atively large and heavy, typically twice the size of an ordinary single-
        phase transformer of the same kVA rating. They are built up to 100 kVA
        single-phase and can be banked for three-phase operation.
          The circuit for the CVT is shown in Figure 8.14 [8.13], and the equiv-
        alent circuit appears in Figure 8.15 [8.14]. Basically, as input voltage
        V declines, the core saturation is reduced, the current I decreases, and
                                                          m
          o
        the net current (I   I ) increases through the series reactance, caus-
                         c
                             m
                                 to rise. The rise compensates for the decline
        ing the output voltage V m
        in V [8.14]. Structures of leakage reactance transformers are shown in
            o
        Figure 8.16 [8.14].
        Standby power systems
        The battery-powered UPS can only deliver power to its critical load for
        the ampere-hour discharge time of the batteries. The battery capacity is
   135   136   137   138   139   140   141   142   143   144   145