Page 187 - Power Quality in Electrical Systems
P. 187

Power Quality Events  169


         250 V
                            Point on wave











                    T b  T a  Phase shift = T – T a
                                    b
        –250 V
        Figure 11.19 Line voltage sag at the 90° point on the wave-
        form of voltage applied to an AC electromagnetic device [11.12]
        [© 2004, IEEE, reprinted with permission].
          The generic voltage tolerance curve for AC relays and contactors is
        shown in Figure 11.20 [11.12]. The experimentally determined values are:
        S1(90 )   5–10 ms, S1(0 )   80–120 ms, VS(0 )   38–75% of nominal
        voltage, VS(90 )   35–60% of nominal voltage. Obviously, the device is
        more tolerant of a voltage sag or interruption that is initiated at the 0  point
        on the voltage wave than the 90  point, for the reason previously stated.

        Correction methods
        Several methods are available to reduce the impact of voltage sags and
        interruptions on relays and contactors. Each method has advantages and
        disadvantages, as follows:


             Voltage
                     ∗
                                     ∗
                  VS ( )- Long voltage sag for  degrees point on wave
                                     ∗
                     ∗
                   SI ( )- Short interruption for  degrees point on wave
                             Influence of the phase shift
                                        3%–10%
         VS (0°)
        VS (90°)


                   α            β
                SI(90°)            SI(0°)        Time
        Figure 11.20  Generic voltage-time tolerance curves for an AC
        electromagnetic device as a function of the point of the voltage
        wave where the sag occurs [11.12].
        [© 2004, IEEE, reprinted with permission]
   182   183   184   185   186   187   188   189   190   191   192