Electric Motor Drive Equipment  179


                                                    Positive DC
                                                       bus



                              Y
                                                    DC output
                  AC input
                                                    to inverter
                  from utility
                                                     section
                           ∆

                   Three
                  winding     ∆
                 transformer                        Negative DC
                                                       bus


         200
                    ∆-Phase input current

          0.0



        −200
         200
                   Y-Phase input current


          0.0


        −200
         200        Line-Phase input current


          0.0
                      .023333         .03     .036667     .043333


        −200                       Seconds
        Figure 12.6 Series connected bridges 12-pulse converter for ASD. Secondary currents for
        wye and delta bridges. Transformer primary line current [12.6].
        [© 1996, IEEE, reprinted with permission]


        resultant rectifier input currents are shown in Figure 12.6 [12.6]. Each
        rectifier input current is typical for a six-pulse rectifier. The resultant
        12-pulse rectifier line current has the 11th and 13th as the lowest-order
        harmonics (see Chapter 5).