Page 202 - Power Quality in Electrical Systems
P. 202

184   Chapter Twelve


           110
                         Conditions: 2.5% unbalance, 5 hp drive, half load
           100                   DC bus C = 56 uF/hp. La = 1%

            90
          Input current harrmonic amplitude (%)  70
            80




            60
            50

            40
            30

            20
            10

             0
              0     5    10    15   20    25   30    35    40   45    50
                                     Harmonic orders
        Figure 12.12 5 hp ASD. 2.5-percent line voltage unbalance, L S    1%. Harmonic spec-
        trum under unbalanced conditions [12.10].
        [© 2004, IEEE, reprinted with permission]
          Restart options are provided on commercial ASDs. Figure 12.13 shows
        a simplified version of the operation between power failure and recovery.
        The dc-bus voltage declines as the bus capacitor discharges while supply-
        ing the inverter. The inverter is shut down by the dc-bus under-voltage trip.
        The motor coasts down. The dc-bus voltage recovers when power is restored.
        The motor and inverter will only restart on a reset command [12.11].

                 Power failure  Power recovery
        Set value: 0
         Main circuit     Under
         DC voltage      voltage



                                          Time
                                                 Figure 12.13  Commercial ASD
           Output                                operations following power fail-
          frequency                              ure, inverter shutdown by DC-
                                                 bus undervoltage trip. No reset
                                                 command. Motor coasts to a stop
                                                 [12.11].
            LU trip         On