Page 47 - Power Quality in Electrical Systems
P. 47

30   Chapter Three


                                    rms variation
            120
            115
           Voltage (%)  110
            105
            100
             95
             90
               0     0.05    0.1   0.15    0.2   0.25    0.3   0.35
                                     Time (ms)
                                       (a)
            150
            100
          Voltage (%)  50 0


            −50
           −100
           −150
               0     25    50    75    100   125   150   175   200
                                     Time (ms)
                                       (b)
                           5
        Figure 3.7 Voltage swell. The top trace is the instantaneous rms value of the
        voltage. The bottom trace is the line-voltage [3.1].
        [© 1995, IEEE, reprinted with permission]
        Voltage “Swell”
        A “swell” is the converse of the sag, and is a brief increase in the rms line-
        voltage. Shown in Figure 3.7 is a voltage swell caused by a line-to-ground
        fault.


        Impulsive “Transient”
        An impulsive “transient” is a brief, unidirectional variation in voltage, cur-
        rent, or both on a power line. The most common sources of impulsive tran-
        sients are lightning strikes (Figure 3.8). Impulsive transients due to
                       6
        lightning strikes can occur because of a direct strike to a power line, or from
        magnetic induction or capacitive coupling from strikes on adjacent lines.
          Note that in this case, the maximum amplitude of the transient cur-
        rent is ~23 kiloamps and the duration of the transient current is tens
        of microseconds. The frequency and amplitude of lightning-induced
        transients vary geographically, as shown in Figure 3.9.

          5
           From IEEE Std. 1159-1995, p. 19.
          6
           Also called lightning “strokes.”
   42   43   44   45   46   47   48   49   50   51   52