Page 135 - Practical Control Engineering a Guide for Engineers, Managers, and Practitioners
P. 135

110   Chapter  Four






                 ~ to-t  •  •  r  r  r  r  ~ 1  1  i·)
                 .a
                 :.=
                 0..
                 ~ to-2   r  r  r  r  r  r  P'  I' I' ···£1




                 -
                 ~
                 j  -tOO
                 !:l.  -200
                   -300~----~~----~~~--~~~~~~~~
                      to-3      to- 2      to-t      tOO       tot
                                      Frequency (Hz)

             FIGURE 4-37  Bode plot for FOWDT process with P-only control (T= 10, D  =  8,
             g  = 2.5*0.3).
             plot for the open-loop transfer function is shown in Fig. 4-37. Now the
             amplitude is always less than unity so even though the phase lag equals
             1800 at a frequency of about 0.05 Hz there is no concern about stability.
                A simulation of proportional-only control for these conditions is
             shown in Fig. 4-38.
                Note the offset between the set point and the process output.
                   0.35
                    0.3
                   0.25
                 ::J  0.2
                   0.15
                    O.t
                   0.05
                     00   tO   20   30   40   50   60   70   80   90   tOO

                     2
                    1.5       . .   .  \  ...  • ..    . .
                 V)
                 "'0
                 ;
                 >-  0
                   -0.5   ...    . ..     . .
                    -t
                      0   tO   20   30   40   50   60   70   80   90   tOO
                                         Time
             FIGURE 4-38  Bode plot for Proportional-only controlled FOWDT process to
             unit set-point step.
   130   131   132   133   134   135   136   137   138   139   140