Page 164 - Practical Control Engineering a Guide for Engineers, Managers, and Practitioners
P. 164

Matrices  and  Higher-Order  Process  Models   139



             .........
              ~~     0~------~--~----,
              ...
              ~
              5'~ -50
             .,~
                 ...
             -~ -100
             ~+
              .a c  -150
              ·~   -200 L-n-4____.____.__. ............... ........,____.___._ .......................... ___.__._ ........................... ___. ............................ ..........~
              ~      1u  .       10-3       10-2       10-1       100
                     0.---------==~~~.-~--~~------~
             .........
              ~~- -100
              ... ~~
              ~  ...
              C)'~  -200
             -+
              M c  -30o
             ..c
              p..
                  ~o~~~~~--~~~~--~~~~~~~~
                     1o-4        1~         1~         1~         ~
                                         Frequency
             F1aURE 5-12  Bode plot of no backflow, integral-only control, three-tank,
             closed-loop.
             is plotted against frequency. This figure is to be compared with Fig. 5-9
             which dealt with the open-loop Bode plot for G,G,. Figure 5-12 shows
             that for low frequencies the magnitude of the Y IS is near unity and the
             phase lag is relatively low.
                In other words, the process output Y follows the set point S fairly
             well at low frequencies, say below 5 x 1o-' Hz. As the frequency of S
             increases, the process output Y does not follow the set point as well-
             there is an attenuation of Y  relative S and there is phase lag. Physi-
             cally, this is to be expected. At low frequencies, the inertia of the pro-
             cess  is  not  enough  to  keep  the  process  output  from  effectively
             following the set point. However, at high frequencies, the inertia is
             such to cause the process output not to follow the set point.

        5-4  Critical Values and Finding the Poles
             In Chap. 3, the poles of the appropriate transfer function for the con-
             trolled system could be found by solving Eq. (3-50) or


                                                                (5-16)

                In these last couple of examples, we have shown that, after replac-
             ing s with jm, Eq. (5-16) essentially becomes a complex equation

                                                                (5-17)
   159   160   161   162   163   164   165   166   167   168   169