Page 392 - Renewable Energy Devices and System with Simulations in MATLAB and ANSYS
P. 392

Microgrid for High-Surety Power: Architectures, Controls, Protection, and Demonstration  379



                            TABLE 14.2
                            Specifications of Short-Circuit Analysis

                            Parameter                                 Value
                                                                     375 V
                            Positive/negative bus voltage V DC
                                                                     10 mF
                            DC bus capacitor C DC
                                                                     1 μH
                            Line impedance from bus capacitor to submodule L s
                            Short-circuit resistor of submodule R s  40 mΩ
                                                                     100 kW
                            Rated power of submodule P r
                                                                     133 A
                            Rated current of submodule I r


                                  800
                                  710
                                  600
                                DC bus voltage (V)  400





                                  200


                                   0
                                    0 0.05  0.2   0.4    0.6    0.8     1
                              (a)                   t (ms)

                                 20 k


                                 15 k
                                Fault current (A)  12 k

                                 10 k


                                  5 k


                                   0
                                    0 0.05  0.2   0.4    0.6    0.8     1
                              (b)                   t (ms)

            FIGURE 14.24  Short-circuit fault waveform. (a) DC bus voltage waveform. (b) Fault current waveform.



              In Figure 14.24, the short-circuit fault occurs in the converter module between positive bus and
            negative bus. It can be seen that the DC bus voltage drops from 750 to 710 V, and the fault cur-
            rent increases to 12 kA within 50 μs. In order to guarantee the load is uninterruptible, the isolation
            breaker must be very fast to avoid DC bus voltage drop. However, the trigger time of a mechani-
            cal breaker is too slow to fulfill the requirement of this application. Thus, a solid-state DC breaker
            should be introduced to the system.
   387   388   389   390   391   392   393   394   395   396   397