Page 151 - Well Control for Completions and Interventions
P. 151

Well Control Surface Equipment                               143


                 • If used, the drilling spool can be positioned below or between the
                   ram preventers. It must have two side outlets of at least 2 in. nomi-
                   nal diameter.
                    There are several possible configurations where an annular pre-
                 venter and two pipe rams are used. One option is to place the blind
                 ram below the pipe ram with the drilling spool between the two-ram
                 preventers. Positioning the blind ram at the bottom allows pipe to be
                 placed in the pipe ram to back-up a leaking blind ram. In addition,
                 the pipe rams can be changed or the annular seal replaced and the
                 blind ram closed.
                    An alternative configuration places the drilling spool between the
                 annular preventer and the ram preventers. When configured this way,
                 it is common to place the bind rams above the pipe rams. This allows
                 the tubing or drill string to be hung off in the pipe rams and the blind
                 rams closed.
              3. Configuration for 10,000 15,000, and 20,000 psi working pressure BOP
                 stacks
                    The minimum requirements for 10,000 15,000, and 20,000 psi
                 BOP stacks is to have:
                 • Annular preventer.
                 • Three ram type preventers (usually a double ram and a single ram
                   preventer).
                 • Kill and choke lines can be connected to the BOP ram outlets pro-
                   viding they meet the required dimensional requirements—nomi-
                   nally 3 in. diameter.
                 • If a drilling spool is used it should have two outlets, one of
                   3 in. nominal diameter, and a second with a 2 in. nominal
                   diameter.
                    The stack can be configured with a double ram preventer block
                 below the annular preventer and immediately above a drilling spool.
                 A single ram preventer is positioned below the drilling spool. Placing
                 the blind (or blind shear) ram between the two pipe rams (above the
                 drilling spool) allows pump in and bleed off with the blind ram
                 closed. Some operators recommend having a second pressure moni-
                 toring and emergency kill line below the lowest ram. In a situation
                 where the bottom pipe ram needs to be closed it would still be possi-
                 ble to monitor well pressure. It could be used to perform a bullhead
                 or lubricate and bleed well kill.
   146   147   148   149   150   151   152   153   154   155   156