Page 171 - Advances in Renewable Energies and Power Technologies
P. 171

144    CHAPTER 4 Performance of MPPT Techniques of Photovoltaic Systems




                                                                               is the maximum
                         where I sens max  is the maximum PV current to be sensed and V adc max
                         input voltage accepted by ADC circuits. The Op-Amp device used in the PV current
                         sensing circuit is the same as the device used in PV voltage-sensing circuit.
                            The terminals of the current sensor ACS754XCB-150 must be connected in se-
                         ries with the PV array as shown in Fig. 4.27. The current passing through the PV
                         array must enter the sensor from its IPþ terminal and exit the sensor from its IP
                         terminal. It is suggested to connect sensor’s IPþ terminal to the PV array positive
                         terminal and the senor’s IP  terminal to one of boost’s coil terminal.




                         3. SMART MAXIMUM POWER POINT TRACKER UNDER
                            PARTIAL SHADING CONDITIONS
                         3.1 PARTIAL SHADING EFFECT

                         PV cells should be connected in parallel and series to increase the current and
                         voltage, respectively, to be suitable for the load. Partial shading occurs when one
                         or more PV cells in the PV array are exposed to lower radiation than the rest of
                         the PVarray. If partial shading occurs to one or more of series PV cells, it will force
                         the partial shading PV cell to work with current higher than the generated current
                         and it will act as a load for the other PV cells. If the current flow in the shaded
                         PV cell is higher than the generated voltage, it will become negative as shown in
                                                                          2
                         Fig. 4.28 for two PV cells in series with 500 and 1000 W/m . It is clear from this
                         figure that the first PV cell works at negative terminal voltage for values of terminal
                         voltage lower than the open-circuit cell of the second PV cell. The relation between
                         the generated power from two series PV systems with variation of output voltage


                                     80

                                               Total Power (W)
                                     60

                                     40
                                    Power (W)  20  500 W/m2



                                      0
                                                                1000 W/m2
                                     -20

                                     -40
                                      -20   -10    0     10    20    30   40     50
                         FIGURE 4.28
                         Terminal voltage across each PV cell of two series PV cells.
   166   167   168   169   170   171   172   173   174   175   176