Page 171 - Applied Process Design For Chemical And Petrochemical Plants Volume III
P. 171

66131_Ludwig_CH10D  5/30/2001 4:31 PM  Page 134










                       134                       Applied Process Design for Chemical and Petrochemical Plants

                         By assuming no entrainment in each condenser tube, the
                       liquid rate out the tube must equal the vapor rate entering
                       the tubes (assuming no noncondensables), so L/G   1, and
                       at steady state, F 2   1.
                         Using the Dowtherm figures cited previously at 20-in. Hg.
                       vacuum,
                             20.8 dynes>cm

                         g      0.0877 lb>ft 3
                            0.5
                        a  b    15.4
                           g
                                   0.5
                       V f   F 1 F 2 a  b
                                  g
                       V f      112 112 115.42     15.4 ft>sec
                         This is the velocity of the vapors in the tube, which will
                       result in flooding at this low pressure.
                         For the condition of 20 psig pressure:
                             13.05 dynes>cm
                                                                             Figure 10-79. Effect of entrance tube taper on flooding velocity. (Used
                         g      0.5587 lb>ft 3                               by permission: Diehl, J. E., and C.R. Kop Company, Chemical Engi-
                                                                             neering Progress Symposium, Heat Transfer, V. 65, No. 92, ©1968.
                            0.5   13.05  0.5                                 American Institute of Chemical Engineers. All rights reserved.)
                        a  b    a      b    4.83
                                 0.5587
                           g
                       F 1      F 2      1

                         Because:
                            0.5                                                  Example 10-11. Desuperheating and Condensing
                        a  b  6 10                                                            Propylene in Shell
                           g
                                        0.5 1.15
                       V f   0.71cF 1 F 2 a  b  d                              See Figure 10-80.
                                       g
                                                                               A refrigeration system requires that 52,400 lb/hr of
                       V f      4.35 ft>sec                                  propylene refrigerant vapor from the compressors be desu-
                                                                             perheated and then condensed.
                         By comparing with solving for the same conditions using
                       a 1-in. tube in the English correlation at 20-in. Hg vacuum,  Propylene inlet: 265 psia and 165°F
                                             42
                       V f   14.02 ft/sec, compared to 15.4 ft/sec from the preced-  Propylene dew point: 265 psia and 112°F
                       ing calculation.                                          Cooling water in: 90°F
                                 42
                         English’s flooding correlation incorporates an entrain-
                       ment load of E/G from 0.01—0.05 lb liquid per lb of vapor.  Assume that this load can be handled best in two units
                         The effect of the tapered inlet tube (as earlier discussed)  operating in parallel. In this scenario, if one condenser
                                                  42
                       as now determined by English is only significant at the  develops trouble, the entire refrigeration system, and con-
                       60° and 75° tapers, both producing about the same     sequently the plant process, is not shut down.
                       increase in vapor capacity. Diehl’s correlation is shown in
                       Figure 10-79.                                         Heat Duty

                       where                                                 Heat content of propylene vapor at 165°F   512 Btu/lb
                             E   superficial liquid entrainment rate, lb/hr/ft 2  Heat content of propylene vapor at 112°F   485 Btu/lb
                          F 1 , F 2   correlation factors defined by equations
                                                                             Sensible heat duty   52,400 (512   485)   1,415,000 Btu/hr
                            V f   superficial flooding velocity of the vapor, ft/sec
                            V f7   superficial flooding velocity of the vapor when inlet  Latent heat of vaporization at 112°F   126 Btu/lb
                                tube taper is 70°, ft/sec                    Latent heat duty   52,400 (126)   6,600,000 Btu/hr
   166   167   168   169   170   171   172   173   174   175   176