Page 176 - Boiler_Operators_Handbook,_Second_Edition
P. 176

Refrigeration & AC                                                                                  161

               it necessary to cover two of the fan discharge screens  ers are readily damaged by the plastic strings of weed
               to restrict airflow enough to maintain an adequate con-  eaters; I even investigated one problem site where the
               denser pressure. Wax coated cardboard hinged on one  Yard workers had elected to write their initials into the
               side with some duct tape did a good job of it but the  fins using a weed eater; needless to say the culprits were
               cardboard had to be flipped back over in cold weather if  easy to identify. The grass and weed eater damage has
               the fan of that section was operated.                the same effect as debris accumulation on the condenser
                    Regular inspections of condensing units are re-  outlet. Unless the damage is so extensive that the fins
               quired because so many things can happen to them.  are torn, bent fins on an air cooled condenser can be re-
               During each inspection of the condensing unit you  paired readily with a device called a fin comb. Even if
               should always look for oily spots around the unit base  none of these obvious conditions of condenser blockage
               and connecting piping; those spots would be refriger-  are evident a regular annual cleaning of the condenser
               ant oil indicating a system leak. Sometimes the units are  coils is recommended.
               mounted on the roofs of buildings which requires a roof
               hatch and/or ladder for access and it’s not uncommon  Water Cooled Condensers
               for the latter to be one that’s carried on a truck. These are     Every source of water for a water cooled condens-
               less susceptible to damage than units mounted at grade  ers can be counted upon to be colder than air except
               level but at the same time are the ones that are frequent-  in the winter. Even water cooled by a cooling tower is
               ly overlooked during normal inspection rounds. Prob-  colder than the temperature of the air. Heat transfer be-
               lems with rooftop condensing units normally fall in the  tween metal and flowing water is considerably higher
               range of blockage of the coils and fins of the condensing  than the heat transfer between metal and flowing air. So,
               unit  by  airborne  contaminants.  Cottonwood  tree  and  water cooled condensers are preferred because they per-
               oak tree pollen is a common problem when the trees are  mit lower saturation temperatures inside the condenser
               blooming and leaves can block the coils in the fall.  which reduces the horsepower requirements of the com-
                    Newer condensing units mounted at ground level  pressor.
               are exposed to other hazards. All new units are similar     You may ask, “Okay, why isn’t my home air condi-
               to a residential unit (Figure 5-31) because the three sid-  tioner water cooled?” Well, if you live in the Southwest,
               ed coil and vertical air discharge make them more effi-  it actually may be water cooled. We call them  evapo-
               cient. A common problem is the accumulation of leaves,  rative condensers (Figure 5-16), and they can be found
               seeds, and small branches that fall onto the condensing  almost anywhere. The refrigerant is piped or connect-
               unit and managed to drift past the fan to settle behind  ed with tubing to coils in a casing where water drips
               the condenser. The bottom tubes of the condenser then  on them to absorb heat as the water evaporates and is
               act as a receiver because tubes higher up have to serve  carried off by air drawn through the evaporative con-
               as that portion of the heat exchanger dedicated to sub-  denser. It requires a pump to circulate the water from
               cooling. The result is an apparent loss of refrigerant  the catch well at the bottom of the condenser to the top
               because more liquid is held in the condenser. Always  where it’s distributed over the tubes. A makeup water
               look through the fan to check for accumulations that can  flow control valve is required to add water from a water
               cause this problem. It’s not unusual for the discharge  supply to replace the water that is evaporated. And, a
               screen to be readily removed for access to remove any  small amount of water must be removed by blowdown
               accumulations;  however,  always  turn  the  unit  off  and  to limit the concentration of solids in the circulated wa-
               disconnect power to the condensing unit before you  ter.  The  operation  and  maintenance of  an  evaporative
               reach your hands and arms through the fan to remove  condenser is very similar to cooling towers which  are
               any accumulation. Don’t forget to put the discharge  discussed later.
               screen back on before restoring power and control. The     Construction of a water cooled condenser is highly
               inlet side of the condenser can also be plugged up with  dependent on the quality of water used to absorb the
               mown grass and debris drawn into the fins by the air-  rejected heat. The condensers for my shipboard refrig-
               flow with the assistance of a lawn mower, weedeater, or  eration plants used seawater that is highly corrosive
               wind. More frequent inspections in the spring when the  and contains all forms plant and animal life. It had to
               pollen and seeds are falling and in the fall when leaves  be  filtered  before  the  section  of  the  circulating  pump
               are falling should be made to ensure the condenser inlet  that forced salt water from the ocean through the filter,
               is clean. Yard workers prove to be a hazard for most con-  the  pump,  condenser,  and  condenser  water  flow  con-
               densing units because the fins on the air cooled condens-  trol valve then back to the ocean. The shell, heads, and