Page 179 - Boiler_Operators_Handbook,_Second_Edition
P. 179

164                                                                               Boiler Operator’s Handbook

               If there isn’t enough liquid entering the evaporator to  Adjustable orifice
               ensure most of its internal surface is exposed to boiling   An adjustable  orifice  produces  a  pressure  drop
               liquid, overall heat transfer will be reduced.       by restricting flow (Figure 5-21). Unlike a capillary the
                    In some of the graphics that follow you will note  pressure drop is generated right at the valve.  As the
               the formation of bubbles within the stream of liquid leav-  name implies an adjustable orifice is manually adjusted.
               ing the throttling device. This always occurs because the  It requires an operator adjust it while observing evapo-
               temperature of the liquid at the outlet of the condenser  rator pressure and outlet temperature. They should only
               is always higher than the saturation temperature main-  be used when the load on the evaporator is very stable
               tained in the evaporator. Also, the ambient temperature  and consistent.
               is usually higher than the evaporator temperature so the
               liquid refrigerant cannot be cooled by air around the liq-  Automatic Expansion Valve
               uid piping. A very small portion of the liquid vaporizes   An automatic expansion valve simply maintains
               absorbing heat from the rest of the liquid to lower its  a constant pressure in the evaporator, (Figure 5-22). In
               temperature to the saturation temperature in the evapo-  addition to the one shown these can be manufactured
               rator.                                               with an external sensing line so the pressure that’s con-
                                                                    trolled is at a different location than the valve outlet. An
               Capillary                                            automatic expansion valve can be used to control the
                    The throttling device for many small units is a sim-  refrigerant flow into an evaporator that has a means of
               ple capillary. An extended length of small diameter tub-  separating the  liquid and vapor so  only vapor leaves
               ing between the outlet of the condenser and the inlet of  the evaporator. That’s normally accomplished with a re-
               the  evaporator  restricts  the  flow  of  refrigerant  (Figure  tention space for separating the liquid and vapor plus
               5-20). As the pressure drops within the refrigerant liquid it  enough room that gas velocity doesn’t carry liquid drop-
               reaches a point of saturation and vapor starts to form. The  lets with it.
               bubbles of vapor take up more space within the narrow
               capillary so the velocity has to increase which results in
               an increase in pressure drop. It only takes a small amount
               of vapor, just a few bubbles, to produce a significant dif-
               ference in pressure drop. The result is a stable flow rate
               through the capillary. Capillary tubing diameters are tab-
               ulated for each refrigerant and capacity.

































                             Figure 5-20. Capillary                            Figure 5-21. Adjustable orifice
   174   175   176   177   178   179   180   181   182   183   184