Page 361 - Boiler_Operators_Handbook,_Second_Edition
P. 361

346                                                                               Boiler Operator’s Handbook


                                                                    times  the  differential  in  inches  divided  by  6356  and,
                                                                    since the differential was zero, the horsepower require-
                                                                    ments as they sat there on the floor should be negligible.
                                                                    Since I had the instruction manual in hand and it clearly
                                                                    stated that the fan had to be installed and the differential
                                                                    has to be at least 80% of the design value he agreed to
                                                                    have an electrician check the motor current. The motor
                                                                    current was three times nameplate rating and that’s why
                                                                    they kept burning them up.
                                                                        It was later, when I examined one of my engineer-
                                                                    ing books, that I discovered the reason for the problem.
                                                                    The differential pressure in the horsepower formula is
                                                                    total pressure, a combination of static and velocity pres-
                                                                    sure differences. Those fans had no static difference but
                                                                    the velocity pressure was there and a lot higher because,
                                                                    without the static resistance, the fan could force more air
                                                                    through to produce a higher velocity and, therefore, a
                                                                    higher velocity pressure. The increased flow and velocity
                                                                    pressure added up to produce the high horsepower that
                                                                    overloaded the motor. This is a lesson for testing any elec-
                                                                    trical device, that contractor had simply wired the fans to
                                                                    a welding connection in the plant. No starter, no overload
                                                                    devices, is it any wonder he was burning up motors?
               Figure 10-85. Propeller fan housing with flow re-        Fans, like pumps, have a theoretical horsepower.
               directed                                             From the story I just told you know that it’s the total
                                                                    pressure across the fan that has to be used. The formula
               some  spin  and  make  them  more  efficient  (Figure  10-  is cfm times total pressure divided by 6356. If all you can
               85). Propeller fans are primarily limited to ventilation   measure is the differential you can calculate the velocity
               services in a boiler plant although they were used in the   pressure. Divide the cfm by the area of the fan discharge
               middle of the last century for forced draft and induced   to get velocity then look up the velocity pressure. Add
               draft service when differentials were low.           velocity and static pressure differentials to get total pres-
                    Some key  things  to know  about propeller fans   sure. Don’t have a table? The velocity is the capacity in
               include the fact that they readily overload their motors   cfm divided by the area of the outlet. Divide the velocity
               if the system doesn’t produce the design resistance. I re-  by 4005 and multiply the result by itself to get velocity
               member visiting a job site in a synthetic fiber plant where   pressure. Add it to the static to get total pressure.
               a contractor had several propeller fans simply sitting on      Many fans and blowers are belt driven. The use of
               the floor and running with temporary wiring. We were   belts will allow an engineer to pick a fan for optimum
               informed that they were testing the fans because the mo-  speed for a given application because any speed can be
               tor on one of them failed and now they’re finding more   established by the proper mix of motor speed and size
               of them are failing. Luckily I was wise enough to pull   of sheave (those pulleys the belts run on). In some cases
               one of the instruction manuals out of the envelope at-  one of the sheaves is adjustable to permit field adjust-
               tached to a lifting eye and read enough to learn the fans   ment of the speed. All these features are very valuable
               were designed for a two inch differential. The drawings   for HVAC equipment where the flow is constant and
               showed the installation would produce that but the fans   the fan can be tuned to achieve the precise required
               sitting on the floor just blowing air were operating with   flow without chewing up added energy with dampers.
               no appreciable differential. I suggested they quit testing   They’re not as valuable in a boiler application where the
               them immediately because they were destroying them   air flow is varied.
               by overloading them.                                     Another advantage of belts is they can slip on start-
                    In turn I was lectured by one of the contractor’s   up to reduce the startup load on the motor, something
               engineers that they couldn’t possibly be overloading   to let go until you’ve checked the instruction manual.
               because fan horsepower is equal to the capacity in cfm   Belts are typically provided to the degree that one belt